Table H2 Common Problems - Continued

Problem

Possible Causes

Solution

Boilers overshooting
setpoint or tripping
aquastat

• Header sensor not installed

correctly

• PID setting require

adjustment

• Adjustable aquastat set too

low

• System pumps are shut

down and not controlled by

or interlocked with the BMS





• BMS is set to ALWAYS

ENABLE

• Check header sensor connections

and installation.

• Adjust PID settings. See para. 4.4.7

• If aquastat is set lower than 200°F,

reset it to 220°F.

• If system pumps are shut down,

check start and stop temperatures

on energy management system.

They should correspond to those

set in the BMS. In addition, interlock

wiring can be run between the BMS

and energy management system to

disable the BMS pumps when

pumps are not running.

• If BMS is set to ALWAYS

ENABLED, change it to START

ENABLED

Modbus Network faults
encountered. Boiler
plant not operating

• BMS or boilers not properly

configured for Modbus

communication

• Refer to Modbus Communication

Manual GF-114. Check all wiring

connections and software menu

settings.