AM Series Modbus Interface Manual

Controller (Managing) Parameters

Holding

Register

Access

Parameter Name

Automatic

Conversion

Range

R

W

200 00C8

X

Controller State

-

See controller state table

201 00C9

X

Controller Status

-

See controller status table

202 00CA

X

Controller Error Code

-

See controller error list

203 00CB

X

Controller Warning Code

-

See controller warning list

204 00CC

X

X

Controller CH setpoint

V

Depending on units °C / °F

205 00CD

X

X

Controller DHW setpoint

V

Depending on units °C / °F

206 00CE

X

X

High Outdoor Air temperature

V

Depending on units °C / °F

207 00CF

X

X

Minimum outdoor air setpoint

V

Depending on units °C / °F

208 00D0

X

X

Low outdoor air temperature

V

Depending on units °C / °F

209 00D1

X

X

Maximum Outdoor air setpoint

V

Depending on units °C / °F

210 00D2

X

X

Outdoor air shutdown
temperature

V

Depending on units °C / °F

211 00D3

X

X

Night Setback

-

Depending on units °C / °F

212 00D4

X

-

Header temperature

V

Depending on units °C / °F

213 00D5

X

-

Outside temperature

V

Depending on units °C / °F

214 00D6

X

-

Cascade Firing Rate

V

0..100%

215 00D7

X

-

Min Firing Rate

V

0..100%

216 00D8

X

-

System pump

V

0/100 or 0..100%

..

-

-

reserved

-

-

299

012B

-

-

reserved

-

-






























OMM-0102_0A