CHAPTER 2: ERROR, STATE, AND, STATUS TABLES

2.1 Lockout Error Codes Table

Lockout errors are indicated by an ‘A’ displayed before the error code number.

“A” Lockout Error Codes

‘A’

Code

Error Name

Int.

#

Description

1

IGNIT_ERROR

1

Three unsuccessful ignition attempts in a row

2

GV Relay Error

2

Failure detected in the GV Relay

3

GV Relay not open error

3

Failure detected in the GV Relay

4

GV Relay not closing error

4

Failure detected in the GV Relay

5

Safety relay error

5

Failure detected in the Safety Relay

6

Safety relay open error

6

Failure detected in the Safety Relay

7

Safety relay closed error

7

Failure detected in the Safety Relay

11

Blocking too long error

11

Control had a blocking error for more than 20 hours in a row.

12

Fan error

12

Fan MF deviation for more than 60 sec

13

Ram error

13

Internal software error

14

Wrong eeprom signature

14

Contents of e2prom is not up-to-date

15

X ram error

15

Internal software error

16

E2prom error

16

No communication with E2prom

17

E2prom error safety C

17

Wrong safety parameters in e2prom

18

E2prom error Calibration table

18

Wrong calibration table parameters

19

State error

19

Internal software error

20

Rom error

20

Internal software error

21

Rom error C

21

Internal software error

22

Air sw not open

22

Air pressure switch not working

23

15MS XRL error

23

Internal software error

24

Air sw not closed

24

Air pressure switch not working

25

Max Temp. Error

25

The external overheat protection is activated

26

Stack error

26

Internal error

27

Flame out too late

27

Flame still present 10 sec. after closing the gas valve

28

Flame error 1

28

Flame is detected before ignition

29

20MS XRL error

29

Internal software error

30

41MS XRL error

30

Internal software error

31

Too many flame failures

31

Three times flame lost during one demand

32

Flow switch not closed

32

Flow switch not working / No flow

33

Flow switch not open

33

Flow switch not working / No flow

34

Flag byte integrity

34

Internal software error

35

AD Hi cpl.

35

Internal software error

36

AD Lo cpl.

36

Internal software error

37

Register error

37

Internal software error