Initial start-up – AERCO BMK 2.0 LN Nat. Gas June 2010 User Manual

Page 39

Advertising
background image

INITIAL START-UP

Combustion Oxygen Level at

45% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

7.2 %

<50 ppm

<30 ppm


40. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

41. Once the oxygen level is within the specified

range at 45%, press the ENTER key to store
the selected blower output voltage for the
45% valve position.

42. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

43. Press the CHANGE key. SET Valve Position

will begin to flash.

44. Press the ▼ arrow key until the SET Valve

Position

reads 30%, then press the ENTER

key.

45. Press the

▼ arrow key until CAL Voltage

30%

is displayed.

46. Press the CHANGE key. CAL Voltage 30%

will begin to flash.

47. The oxygen level at the 30% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<30 ppm

48. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

49. Once the oxygen level is within the specified

range at 30%, press the ENTER key to store
the selected blower output voltage for 30%
valve position.

50. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

51. Press the CHANGE key. SET Valve Position

will begin to flash.

52. Press the ▼ arrow key until the SET Valve

Position

reads 16%, then press the ENTER

key.

53. Press the

▼ arrow key until CAL Voltage

18%

is displayed.

54. Press the CHANGE key. CAL Voltage 18%

will begin to flash.

55. The oxygen level at the 18% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

18% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<30 ppm

56. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

57. Once the oxygen level is within the specified

range at 18%, press the ENTER key to store
the selected blower output voltage for 18%
valve position.

58. This completes the Natural Gas combustion

calibration procedure. Skip the Propane
Combustion Calibration procedure in
paragraph 4.4 and proceed directly to the
Proceed directly to the Unit Reassembly
procedure in paragraph 4.5.

4-5