Chapter 6 safety device testing, 1 testing of safety devices, 2 low gas pressure fault test – AERCO BMK 2.0 LN Nat. Gas June 2010 User Manual

Page 51: Safety device testing

Advertising
background image

SAFETY DEVICE TESTING

CHAPTER 6 SAFETY DEVICE TESTING

6.1 TESTING OF SAFETY DEVICES

Periodic safety device testing is required to
ensure that the control system and safety
devices are operating properly. The boiler
control system comprehensively monitors all
combustion-related safety devices before, during
and after the start sequence. The following tests
check to ensure that the system is operating as
designed.

Operating controls and safety devices should be
tested on a regular basis or following service or
replacement. All testing must conform to local
codes such as ASME CSD-1.

NOTE

MANUAL and AUTO modes of operation
are required to perform the following
tests. For a complete explanation of these
modes, see Chapter 3.

NOTE

It will be necessary to remove the front
door and side panels from the unit to
perform the following tests.

WARNING

ELECTRICAL VOLTAGES IN THIS
SYSTEM MAY INCLUDE 120 AND 24
VOLTS AC. POWER MUST BE RE-
MOVED PRIOR TO PERFORMING
WIRE REMOVAL OR OTHER TEST
PROCEDURES THAT CAN RESULT
IN ELECTRICAL SHOCK.

6.2 LOW GAS PRESSURE FAULT TEST

Refer to Figure 6-1 and ensure that the leak
detection ball valve located at the high gas
pressure switch is closed.

1. Remove the 1/8 “ plug from the ball valve at

the low gas pressure switch shown in the
lower portion of Figure 6-1.

2. Install a 0 – 16 “ W.C. manometer or a W.C.

gauge where the 1/8" plug was removed.

3. Slowly open the ball valve near the low gas

pressure switch.

4. Place the unit in Manual Mode and adjust

the air/fuel valve position (% open) between
25 and 30%.

5. While the unit is firing, slowly close the

external manual gas shut-off valve.

6. The unit should shut down and display a

LOW GAS PRESSURE

fault message at

approximately 2.6” W.C. The FAULT indi-
cator should also start flashing.

Figure 6-1

Low & High Gas Pressure Testing

7. Fully open the external manual gas shut-off

valve and press the CLEAR button on the
Control Box.

8. The fault message should clear and the

FAULT

indicator should go off. The unit

should restart.

9. Upon test completion, close the ball valve

and remove the manometer. Replace the
1/8 “ plug removed in step 1.

6-1

Advertising