Appendix i – AERCO BMK 2.0 LN for Mass. only User Manual

Page 107

Advertising
background image

APPENDIX I

I-1

RECOMMENDED PERIODIC TESTING CHECK LIST

WARNING

NOTE: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as

designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property

damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive

maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.

Item Frequency

Accomplished

by

Remarks

See indicated sections of this manual for detailed procedures

Gages, monitors and

indicators

Daily Operator

Make visual inspection and record readings in

operator log

Instrument and

equipment settings

Daily

Make visual check against factory recommended

specifications

Weekly

Operator

Verify factory settings

Firing rate control

Semiannually

Service

technician

Verify factory settings

Annually

Service

technician

Check with combustion test equipment- see

section 7.4

flue, vent, stack or

intake air duct

monthly

Operator

Visual inspection for condition or obstructions

Igniter

Weekly

Operator

see section 7.2

main fuel valve

valve position

Weekly

Operator

Check position indicator

leakage test

annually

Service

technician

Close manual fuel supply valve and test for

pressure on down stream valve port

Combustion safety

flame failure

weekly

Operator

Close manual fuel supply valve check safety

shutdown timing

flame signal strength

weekly

Operator

Read signal with meter and log see section 7.3

low water fuel cut off

and alarm

weekly

operator

See section 6.3

slow drain test

Semiannually

operator

Perform a slow drain test in accordance with

ASME Boiler and Pressure

Vessel Code section IV

high limit safety control

test

annually

Service

technician

See section 6.4

operating control

annually

Operator

See section 3.2

low air pressure

monthly

Operator

See section 6.6

high and low gas

pressure interlocks

monthly

Operator

See section 6.2

air valve purge position

switch

annually

Service

technician

See section 6.6

low fire position switch

Annually

Service

technician

See section 6.7

safety valves

as required

Operator

As per A.S.M.E. Boiler and Pressure Vessel

Code section IV

inspect burner

components

Semiannually

Service

technician

See section 7.6

Advertising