SAFETY DEVICE TESTING

6-4

Figure 6.4

Blower Proof Switch Location and Wiring

6.9 SSOV PROOF OF CLOSURE
SWITCH

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the Safety Shut-Off Valve (SSOV)

cover (see Fig. 6.5).


NOTE:

For units with IRI gas trains, the proof of
closure switch is located in the downstream
SSOV (part no.69005) shown in Fig. 6.5. A
second (upstream) SSOV (part no. 69038)
is also provided, however it does not
contain a regulator and looks physically
different. Refer to drawings AP-A-796-M &
AP-A-801-M (De-Rated) in Appendix F for
IRI gas trains.



3. Disconnect either wire #149 or #148 from

the SSOV.


4. The unit should fault and display SSOV

SWITCH OPEN.


5. Replace the wire previously disconnected

and depress the CLEAR button.


6. Start the unit.

7. Disconnect the wire again when the unit

reaches the purge cycle.


8. The unit should shut down and display

SSOV FAULT DURING PURGE.

9. Replace the wire previously disconnected

and depress the CLEAR button. The unit
should restart.


SSOV

ACTUATOR

COVER

SSOV

ACTUATOR

COVER

SCREW

Figure 6.5

SSOV Actuator Cover Screw Location

6.10 PURGE SWITCH OPEN DURING
PURGE

1. Set the unit’s ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the air/fuel valve cover by rotating

the cover counterclockwise to unlock it and
then pulling it towards you (see Fig. 6.6).


3. Disconnect one of the two wires from the

purge position switch (Fig. 6.7) and start the
unit.


4. The unit should begin to start, then shut

down and display PRG SWITCH OPEN
DURING PURGE.


5. Replace the wire on the purge position

switch and depress the CLEAR button. The
unit should restart.