Appendix a – AERCO KC1000 Low NOx Boiler equipped with C-More version 3.04 User Manual

Page 76

Advertising
background image

APPENDIX A

A-2

BOILER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

SETUP MENU

Password

Allows password to be entered.

Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.

Language

English Only

Time

Displays time from 12:00am to 11:59pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in
degrees Fahrenheit (°F) or degrees Celsius (°C).
Default is °F.

Comm Address

For RS-485 (MODBUS) communications (0 to 255).
Default address is 0. RS-232 should have its own
(programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.

Software Version

Identifies the current software version of the control
box.

CONFIGURATION MENU

Internal Setpoint

Allows internal setpoint to be set . Default is 130°F.

Unit Type

Allows selection of Boiler or Water Heater. Default
is Boiler.

Unit Size

Sets unit size from 0.5 to 3.0 MBTUs. Default is 1.0
MBTU.

Boiler Mode

It allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor
Reset Mode. Default is Constant Setpoint Mode.

Remote Signal

Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. The factory default is
4-20 mA/1-5V.

Bldg Ref Temp

Allows the building reference temperature to be set
when operating a boiler in the Outdoor Reset Mode.
Default is 70°F.