CHAPTER 9: BCM MODBUS AND ADDRESS ASSIGNMENTS

OMM-0093_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page

95 of 108

GF-136-C

Ph.: 800-526-0288

PRI: 06/24/2013

Table 9-4: BCM Standard Holding Register Address Mapping (Continued)

Modbus Data

Address

Menu Item

Units and Range

Default

(Comments)

OPERATING DATA REGISTERS (Continued)

1020

Operating Mode

enum (0, 1, 2, 3, 6)

0: Standby

1: Space Heating

2: DHW

3: Check

6: Test

(Read Only)

1100

Linked BMM

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1101

Inserted BMM

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1102

BMM in Check Mode

Flags (0 -255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1103

BMM Flame Status

Flags (0 – 255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1104

BMM Alarm Status

Flags (0 – 255)

Bit 0: BMM #0

to

Bit 7: BMM #7

(Read Only)

1108

BMM Maximum Modulation Level

0 – 100% (Value x

10)

(Read Only)

1109

Pump Modulation Output

0 – 10V

(Read Only)

1200

Monitor Only

0 – 100%

(Read Only) Global modulation

level from Cascade Manager

2n00

BMM #n Error Code

(n = 0 – 7)

0 – 0xFFFF

(Read Only)

2n02

BMM #n Outlet Temperature

(n = 0 – 7)

14°F to 212°F (-10°C

to 100°C) (Value x 10)

(Read Only)

2n08

BMM #n Actual Modulation

Level (n = 0 – 7)

0 – 100%

(Read Only)