10/14

Siemens

Modulating control valves with magnetic actuators, PN16

CA1N4455en

Building Technologies

15.12.2009

Functional valve data

PN class

PN 16 to EN 1333

Permissible operating pressure

1 MPa (10 bar)

Differential

pressure

Δp

max

/

Δp

S

Refer to table "Type summary", page 2

Leakage rate at
Δp = 0.1 MPa (1 bar)

A

→ AB max. 0.02 % k

VS

(to DIN EN 1349)

B

→ AB < 0.2 % k

VS

depending on operating

conditions

Valve characteristic

1)

Equal percentage, n

gl

= 5.3 to VDI / VDE 2173 or

linear, optimized near the closing point

Permissible

media

MX..461..

Chilled and low-temperature hot water, water
with anti-freeze;
Recommendation: water treatment to VDI 2035

MX..461..P

Mineral oils SAE05 ... SAE50, mineral-oil-based
diesel fuels, heat transfer oils

Medium temperature

1...130 °C

Stroke resolution

ΔH / H

100

1 : 1000 (H = stroke)

Hysteresis typically

3

%

Position

when

deenergized

A

→ AB closed

Mounting position

Upright to horizontal

Mode

of

operation

Modulating

Manual operation

Possible, max. 90 %

Materials

Valve body

Cast iron EN-GJL-250

Plug

CrNi steel (X12CrNiS18 8)

Seat Brass

(CuZn39Pb3)

Valve stem seal

MX..461.. EPDM (O-ring)

MX..461..P Fluororubber – FPM product (Viton)

Bellows

Tombac (CuSn6), bronze (CuSn9), CrNi steel

Dimensions / weight

Dimensions

Refer to "Dimensions", page 12

Weight

Refer to "Dimensions", page 12

Norms and standards

CE conformity

to EMV-requirements


2004/108/EC

Immunity EN

60730-1:2000/A16:2007

2)

Emission EN

60730-1:2000/A16:2007

Electrical

safety

60730-1

Protection class

Class III to 60730

Pollution degree

Class 2 to EN 60730

Housing

protection

Upright to horizontal


IP54 to EN 60529 (with M20 cable gland)

Vibration

3)

IEC

60068-2-6

(1 g acceleration, 1...100 Hz, 10 min)

Conform

to

UL

standards

CSA,

Canada

C-tick

UL 873
C22.2 No. 24
N 474

Environmental compatibility

ISO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally compatible

products)

RL 2002/95/EG (RoHS)

Permissible operating pressure

PED 97/23/EC

Pressure accessories

As per article 1, section 2.1.4

Fluid group 2:

DN15…DN50 • Without CE-marking as per article 3, section 3

(sound engineering practice)

DN 65 • Category I, module A, with CE-marking

1)

Can be selected via DIL switch

2)

Transformer 160 VA (e.g. Siemens 4AM 3842-4TN00-0EA0)

3)

In case of strong vibrations, use high-flex stranded wires for safety reasons.