AERCO MXG-461 Series Control Valve - Manufactured by Siemens User Manual

Page 5

Advertising
background image

5/14

Siemens

Modulating control valves with magnetic actuators, PN16

CA1N4455en

Building Technologies

15.12.2009

YF – Function

no function

fully open

closed

Con

n

ecti

ons

Transf

er

X

G0

Y

YM

X

G

Y

X

YF

G0

G

Y

YM

YF

YM

G

YF

G0

44

55

Z

10

100 %

0 %

Y

0 %

100 %

100 %

0 %

Y

0 %

100 %

Y

0 %

100 %

100 %

0 %

A

AB

A

AB

A

AB

V

V

V

Func

tio

n • YF not connected

• valve will follow the Y-signal

• YF connected to G
• valve will fully open control

path A  AB

• YF connected to G0
• valve will close control path

A  AB


1. Hand wheel position MANUAL (open) or OFF (close)
2. Forced control signal YF
3. Signal input Y

The MX..461.. and MX..461..P magnetic valves are
factory-calibrated at 0 % and 100 % stroke.

When commissioning the valves, however,
(especially under extreme conditions of use) there
may still be some leakage via control path A

→ AB

with a 0 % stroke control signal (DC 0 V, DC 2 V or
DC 4 mA).
In this case, the valve can be recalibrated simply
and quickly:
1. Hand wheel [2] in AUTO-position
2. Use a pointed implement (ø 2 mm) to operate the

button in the opening [3] once

3. While recalibration is in progress, the LED [5] is

flashing green for approximately 10 seconds.
The valve will be briefly closed and fully opened.

If the electronics module is replaced, the valve’s
electronics must be recalibrated. For that, the hand
wheel must be set to AUTO.

Forced control input
YF

Signal priority

Calibration