CONTROL PANEL OPERATING PROCEDURES

3-5

NOTE

The Outdoor Temp display item shown with an asterisk in Table 3-2 will

not be displayed unless the Outdoor Sensor function has been enabled

in the Configuration Menu (Table 3-4).

Table 3-2. Operating Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Status Message

Active Setpoint

40°F

240°F

Aux Temp

30°F

245°F

Outdoor Temp*

-70°F

130°F

Valve Position In

0%

Max Valve

Position

Flame Strength

0%

100%

Run Cycles

0

999,999

Run Hours

0

999,999

Fault Log

0

19

0

Table 3-3. Setup Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Passsword

0

9999

0

Language

English

English

Time

12:00 am

11:59 pm

Date

01/01/00

12/31/99

Unit of Temp

Fahrenheit

Celsius

Fahrenheit

Comm Address

0

127

0

Baud Rate

2400

4800

9600

19.2K

9600

Software

Ver 0.00

Ver 9.99

3.6. CONFIGURATION MENU

The Configuration Menu shown in Table 3-4

permits adjustment of the Internal Setpoint

(Setpt) temperature regardless of whether the

valid password has been entered. Setpt is

required for operation in the Constant Setpoint

mode. The remaining options in this menu

require the valid password to be entered, prior to

changing existing entries. This menu contains a

number of other configuration settings which

may or may not be displayed, depending on the

current operating mode setting.

NOTE:

The Configuration Menu settings shown in Table

3-4 are factory set in accordance with the

requirements specified for each individual order.

Therefore, under normal operating conditions,

no changes will be required.