SAFETY PRECAUTIONS

1-3

1. INSTALLATION OF CARBON MONOXIDE DETECTORS

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl

space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be

installed on the next adjacent floor level.

. At the time of installation of the side wall

horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired

carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas

equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery

operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the

dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be

the responsibility of the property owner to secure the services of qualified licensed professionals for the

installation of hard wired carbon monoxide detectors.

b. In the event that the requirements of this subdivision can not be met at the time of completion of

installation, the owner shall have a period of thirty (30) days to comply with the above requirements;

provided, however, that during said thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS.

3.

Each carbon monoxide detector as required in

accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS

certified.

SIGNAGE

4.

. A metal or plastic identification plate shall be permanently mounted to the exterior of the

building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal

for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no

less than one-half (1/2) inch in size,

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

INSPECTION

(b)

. The state or local gas inspector of the side wall horizontally vented gas fueled

equipment shall not approve the installation unless, upon inspection, the inspector observes carbon

monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1

through 4.

EXEMPTIONS

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most

current edition of NFPA 54 as adopted by the Board; and

: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or

structure separate from the dwelling, building or structure used in whole or in part for residential

purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.

1. Detailed instructions for the installation of the venting system design or the venting system

components; and

When

the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting

system design or venting system components with the equipment, the instructions provided by the

manufacturer for installation of the equipment and the venting system shall include:

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.

1. The referenced "special venting system" instructions shall be included with the appliance or

equipment installation instructions; and

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does

not provide the parts for venting the flue gases, but identifies "special venting systems", the following

requirements shall be satisfied by the manufacturer: