ECS Upgrade for SW Double Wall Heaters, Kits 27035, 27036, 27037

Technical Instruction Document

TID-0142_0A

12/30/2014

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 14 of 24

1. With the Control Box door open, set the ON/OFF POWER switch on the right side to the ON

position. The Temperature Controller will initiate a self-test for approximately 3 seconds.
Following the self-test, the top display will show the current outlet water temperature of the
Heater and the lower display will show the current setpoint temperature stored in memory
(default = 140°F).

2. Ensure that the Temperature Controller is set to the AUTO (automatic) mode and the AUTO

indicator is lit. If the MAN indicator is lit, press the AUTO/MAN button to toggle the mode
setting. Indicator OP1 should also be lit.

3.

If the lower display does not show the desired setpoint temperature, press the ▲ or ▼
arrow button to change the display to the desired value.

4. Two seconds after

the ▲ or ▼ arrow button is released, the display will blink to indicate

that the Temperature Controller has accepted and stored the displayed value.

Figure 2-6. Temperature Controller Installation