ECS Upgrade for SW Double Wall Heaters, Kits 27035, 27036, 27037

Technical Instruction Document

TID-0142_0A

12/30/2014

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288 Page 15 of 24

Table 2-1. Temperature Controller Operating Controls, Indicators & Displays

CONTROL or
INDICATOR

MEANING

FUNCTION

OP1

Output 1 Indicator

OP1 lights when a 4 to 20 mA signal is being supplied
to the ECS Valve Actuator

OP2

Output 2 Indicator

Not used for the ECS application

SP2

Setpoint 2 Indicator

Not used for the ECS application

REM

Remote Setpoint
Indicator

REM lights when the ECS is set up to be controlled by a
Remote (Modbus) signal. REM will also flash when Modbus
communication is active.

Auto/Manual Button
and Indicators

When button is pressed, the Controller is toggled between
the automatic (AUTO) and manual (MAN) modes.
AUTO lights when in the automatic mode.
MAN lights when in the manual mode.

Run/Hold Button and
Indicators

Not used for ECS application

Page Button

Press Page button to select a new list of parameters

Scroll Button

Press Scroll button to select a new parameter in a list

Down Button

Press to decrease the value shown in the lower display

Up Button

Press to increase the value shown in the lower display

NOTE:

External power at 120 to 240 VAC, 50/60 Hz is required to operate
the circuitry contained in the ECS Control Box. Power connections
are made internally by routing the power wiring through the cutout
provided on the right side of the Control Box.

2.5.5 Wiring the ECS Control Box for the Circulator and Temperature Control

To wire the Circulation Pump and Thermocouple into the ECS control box, follow these steps:

1. Loosen the captive Phillips head screw on the right front portion of the Control Box (Figure

2- to open the hinged door.

2. Swing open the door and loosen the captive Phillips head screw at the top of the recessed

panel (Figure 2-8). Swing down the panel to access terminal block TB-2 (Figure 2-9).

3. Circulator Electrical connections: Observe all applicable codes and safety procedures

when connecting to power supply. The motor is impedance protected, and does not require
overload protection. Either colored wire from the pump’s capacitor box can be attached to
either colored wire from the control box power supply. There is no “hot” or “common” wire
leading from the capacitor box. Typical installation would be to attach the white wire to
the white (common) power supply wire and either the yellow or blue wire to the black (hot)
power supply wire. The pump cannot run backwards.