Missing label compensation – CON-TECH CS2000-QD User Manual

Page 13

Advertising
background image

- 11 -

Missing Label Compensation

Overview:

The CS2000 has the capability to detect a single missing label and output a stop pulse as

though the label were present. In order for Missing Label Compensation to function properly the

operator must first: a) have Pulse Output selected - see Program Mode (page 12) for more

information. b) adjust the label sensitivity - see Easy Setup (page 10) for more information. c)

have the labeling machine set to desired speed.

Enabling Missing Label Compensation:

1.

Make sure a label is under the sensing area.

2.

Depress the push-button until the green LED begins flashing at a slow rate

(5 sec.), then release. If the green LED flashes at a fast rate it indicates that the

label was not positioned correctly and you need to start over.

3.

Jog 1 label.

Missing Label Compensation is now enabled and should function correctly.

Disabling Missing Label Compensation:

1.

Depress the push-button until the green LED begins flashing (5 sec.), then release.

2.

Depress the push-button once again to disable.

*You can also disable Missing Label Compensation by selecting Level Shift Output. Refer to

Program Mode (page 12) for more information.

Advertising
This manual is related to the following products: