Connect your wires, Conventional systems – Braeburn 1220NC User Manual

Page 4

Advertising
background image

3

Terminal Function Description

Rc

Input

24 Volt AC Cooling Transformer

(Dual Transformer Systems Only)

Rh

Input

Power Connection (24 Volt AC Heating

Transformer or Millivolt Power Source)

O

Output

Reversing Valve (Cool Active)

B

Output

Reversing Valve (Heat Active)

Y1

Output

1st Stage Compressor

G

Output

Fan Control

W1

Output

1st Stage Conventional Heat

C

Input

24 Volt AC Transformer Common

Connect Your Wires

3

Wiring Terminations

Terminal Function Description

W1/E

Output

(W1) 1st Stage Conventional Heat

(E) Emergency Heat Relay

W2

Output

2nd Stage Heat / Auxiliary Heat

Additional Terminations (1220NC only)

1 HEAT / 1 COOL Single or Dual Transformer

Set Installer Switch to CONV

Rh 24 Volt AC Power (heating transformer) [note 2]
Rc
24 Volt AC Power (cooling transformer) [note 2]
W1
Heat Relay (appears as W1/E on 1220NC)
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

Typical Wiring Configurations

NOTE: The “Installer Switch” option will be configured in the next step.

Conventional Systems

Heat Only or Millivolt

Set Installer Switch to CONV

Rh Power Connection

W Heat Relay (appears as W1/E on 1220NC)

G Fan Relay [note 4]

C 24 Volt AC Transformer Common [note 1]