Back to Back Assembly:

Where two rows of racks are required, two rack assemblies may be

installed back to back.
Frame Location:

Locate back to back frames relative to each other as shown in

Figure 14, such that the rear cross brace attachment holes align

for the two adjoining frames (The frames will be facing opposite

directions). All braces must be installed, as described previously,

except that a single bolt may be used to connect the front and

rear frames and respective cross braces. The ½-13 x 1.50” long

bolt supplied with the rack is to be replaced by a ½-13 x 2 ¼” long

(supplied with racks).
When placed back to back, there must be enough distance between

the frames to allow all of the braces (four total) to be installed. The

“X” distance between anchor bolt holes should be as noted in Table

1 (see Figure 15).
Two step standard racks placed back to back do not need to have

the frames bolted together. For 2 step EP1 racks a bolt assembly is

required (C&D part # REO5253 purchased separately). Contact C&D

for more details.

The EP racks have anchor bolt slots with a 1.06” x 0.69” (26.9 mm x

17.5 mm) for One Tier and Two Step rack models and a 1.06” x 0.81”

(26.9 mm x 20.6 mm) for Two Tier and Three Tier rack models.
The distance between the anchor bolt locations when the racks are

placed back to back is shown in Table 1 and Figure 15.
Note: There may be a de-rating of anchor bolt load ratings due to the

proximity of holes. Reference anchor bolt manufacturer’s data for

information.

ADDITIONAL INSTRUCTIONS FOR MULTI-RACK ARRANGEMENTS

Table 1

Front of Rack A

Front of Rack B

Back of

Racks A & B

Back to Back Assembly

Anchor Bolt

Center Distance

"X"

Anchor Bolt distance (center to center)

racks back to back

NOTE:
Anchor selection is determined by the anchor type, the diameter of the anchor, the depth of embedment

and anchor spacing. The selection of the anchor bolt must be reviewed by a structural engineer to ensure

that the racks will meet the seismic rating for the EP racks.

FIGURE 15

FIGURE 14

RDC Rack

Inches

mm

Inches

mm

1 Tier

3.95

100

4.32

110

2 Tier

3.88

99

4.08

104

2 Step (Std & EP1)

3.63

92

5.67

144

2 Step (EP2)

4.01

102

4.26

108

3 Tier (EP1)

4.64

118

3.88

99

3 Tier (EP2)

4.26

108

4.24

108

"X" Distance

See Figure 15

Anchor Bolt Distance

RS02098/1011/CD