Installation instructions (cont’d), Facts to consider about the location (cont* *d) – Kenmore 153.337002 User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cont’d)

Facts to Consider About the

Location (cont* *d)

Figure 2

ROOM INSTALLATION

(ACCEPTABLE)

A room is any enclosure which is at least 16* times
greater than the total volume of all the gas fired appli­
ances within the enclosure.

Figure 3

ALCOVE INSTALLATION

(ACCEPTABLE)

An alcove suitable for the installation of a water heater is a
restricted section of a room not separated from the room
by a door or partition and which meets the minimum
clearances for the specific model water heater listed
below.

*When the ceiling height exceeds 8 feet, you are only

allowed to consider 8 feet when calculating the total vol­

ume of the enclosure.

!2" MAX.

VENTILATION

AIR

OPENINGS

I

DOOR

FRONT VIEW

OF DOOR

12" MAX.

3" MIN.

AIR DUCT

Figure 4

Figure 5

AWARNING

Minimum

clearances

between

the

water

heater

and

combustible construction are listed below:
Minimum Side & Rear Clearances — I"
Minimum hx>nt clearance from jacket to closet door — 4"

Minimum

ceiling clearance from jacket top to com­

bustible ceiling — 18".

Combustion Air and

Ventilation for Appliances

Located in Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,

through openings not furnished with doors, are considered a
part of the unconfined space

In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion, ventilation and dilution of flue

gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional air may need to be provided using the methods

described in Combustion Air and Ventilation for Appliances
Located in Confined Spaces, b.

Combustion Air and

Ventilation for Appliances

Located in Confined Spaces

Confined Space is a space whose volume is less than 50 cubic

feet per 1,000 Btu per hour of the aggregate input rating of all

appliances installed in that space.

a. ALL AIR FROM INSIDE BUILDINGS:

(See Figures 1 through 6)

The confined space shall be provided with two permanent
openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The total
input of all gas utilization equipment installed in the com­
bined space snail be considered in making this determination.
Each opening shall have a minimum free area of one square

inch per 1,000 BTU per hour of the total input rating of all

gas utilization equipment in the confined space, but not less

than 100 square inches. One opening shall commence within

12 inches of the top and one commencing within 12 inches

of the bottom of the enclosure.

Figure 6

b. ALL AIR FROM OUTDOORS:

(see Figures 7 through 9,

page 12)

The confined space shall be provided with two permanent

openings, one commencing within 12 inches of the top and
one commencing within 12 inches from the bottom of the
enclosure. The openings shall communicate directly, or by
ducts, with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.

11

Advertising
This manual is related to the following products: