Start up conditions, Caution, Start up conditions -25 – Kenmore POWER MISER 153.336261 User Manual

Page 23: Troubleshooting guide, Property damage hazard

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TROUBLESHOOTING GUIDE

Start Up Conditions

Thermal Expansion

CAUTION

Property Damage Hazard

Avoid water heater damage.

■ Install thermal expansion tank or device if necessary.

■ Contact qualified installer or service agency.

Water supply system may, because of such events as high line

pressure, frequent cut-offs, and the effects of water hammer

have installed devices such as pressure reducing valves, check

valves, back flow preventers, etc., to control these types of

problems.

When

these

devices

are

not

equipped

with

an

internal by-pass, and no other measures are taken, the devices

cause the water system to be closed. As water is heated, it
expands (thermal expansion) and closed systems do not allow

for the expansion of heated water.

The water within the water heater tank expands as it is heated

and increases the pressure of the water system. If the relieving

point of water heater’s temperature-pressure relief valve is

reached,

the

valve

will

relief

the

excess

pressure.

The

temperature-pressure relief valve is not intended for the

constant relief of thermal expansion.

This is an unacceptable

condition and must be corrected.

It is recommended that any devices installed which could create

a closed system have a by-pass and/or the system have an

expansion tank or device to relieve the pressure built by thermal

expansion. Themal expansion tanks are available from Sears

stores and through the Sears Service Centers. Contact the

local

plumbing

inspector,

water

supplier

and/or

the

Sears

Service Center for assistance in controlling these situations,

see Figure 26.

Thermal Expansion Tank Specifications

Model

Number

Tank

Capacity

In Gallons

Dimensions

in Inches

Pipe

Fitting

On Tank

Diameter

Length

153.331020

2

8 (203 mm) 12-3/4 (323 mm) 3/4” Male

153.331050

5

11 (279 mm) 14-3/4 (375 mm) 3/4” Male

Expansion Tank Sizing Chart

Expansion

Tank

Capacity

Needed

Inlet*

Water

Pressure

Water Heater Capacity (Gallons)

30

40

50

66

80

40psi

2

2

2

5

5

50psi

2

2

2

5

5

60psi

2

2

5

5

5

70psi

2

2

5

5

5

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or

regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air

charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

FIGURE 26.

Strange Sounds

Possible noises due to expansion and contraction of some

metal parts during periods of heat-up and cool-down do not

represent hamful or dangerous conditions.

Condensation causes sizzling and popping within the burner

area

during

heating

and

cooling

periods

and

should

be

considered normal. See

Condensation

section.

Draft Hood Operation

Check

draft

hood

operation

by

performing

a

worst

case

depressurization of the building. With all doors and windows

closed, and with all air handling equipment and exhaust fans

operating such as furnaces, clothes dryers, range hoods and

bathroom fans, a match flame should still be drawn into the

draft hood of the water heater with its burner firing. If the flame

23