Carrier 62ME User Manual

Page 52

Advertising
background image

52

Table 3 — Electrical Data With VAV Option (cont)

LEGEND

*The VAV option is not available on 62M040 units.

†Fused disconnect only.

**Exhaust and supply fan motors are 230-3-60.

UNIT SIZE

62M*

VFD

VOLTAGE

V-Ph-Hz

ERV

WHEEL

FLA

VFD

CURRENT

INPUT

VALUE

AMP

EXHAUST AND SUPPLY

FAN MOTOR

HEATER

SIZE
(kW)

POWER SUPPLY

PRE-HEATER

(Optional)

FLA

DISCONNECT

(Optional)

NEC - FLA

Hp

FLA

MCA

MOCP

Amps

Fuse Size†

Amps

285

208/230-3-60

0.6

8.2

6.8

2

17.39

20.57

26.74

40

25

5

29.95

36.28

39.31

12.57

60

35

8

37.49

45.70

46.85

20.11

45

10

42.52

51.99

51.99

25.13

50

460-3-60

4.2

3.4

8.82

10.42

13.54

30

12

5

15.11

18.27

19.82

6.28

17.5

8

18.88

22.98

23.59

10.05

20

10

21.39

26.12

26.12

12.57

40

25

575-3-60

3.6

2.7

7.66

8.97

11.66

30

10

5

12.68

15.26

16.69

5.03

15

8

15.70

19.03

19.71

8.04

17.5

10

17.71

21.54

21.72

10.05

20

330

208/230-3-60

1.2

8.2

6.8

2

17.99

20.57

26.74

40

25

8

38.09

45.70

46.85

20.11

60

45

10

43.12

51.99

51.99

25.13

50

15

55.69

67.70

67.70

37.70

80

60

460-3-60

4.2

3.4

9.15

10.42

13.54

30

12

8

19.20

22.98

23.59

10.05

20

10

21.71

26.12

26.12

12.57

40

25

15

28.00

33.98

33.98

18.85

30

575-3-60

3.6

2.7

7.83

8.97

11.66

30

10

8

15.87

19.03

19.71

8.04

18

10

17.88

21.54

21.72

10.05

20

15

22.91

27.82

27.82

15.08

40

25

430

208/230-3-60

1.2

11.3

9.6

3

24.03

28.13

36.56

60

35

8

44.14

53.26

56.67

20.11

80

50

10

49.16

59.54

61.69

25.13

60

15

61.73

75.25

75.25

37.70

100

70

460-3-60

5.6

4.8

12.07

14.06

18.28

30

18

8

22.12

26.63

28.33

10.05

40

25

10

24.63

29.77

30.85

12.57

30

15

30.91

37.62

37.62

18.85

60

35

575-3-60

4.8

3.9

10.29

12.05

15.66

30

15

8

18.33

22.10

23.71

8.04

20

10

20.34

24.61

25.72

10.05

25

15

25.37

30.90

30.90

15.08

40

30

550

208/230-3-60

1.2

17.8

15.2

5

37.16

44.53

57.89

80

50

8

57.26

69.66

78.00

20.11

100

70

10

62.29

75.95

83.02

25.13

80

15

74.85

91.65

95.59

37.70

200

90

460-3-60

9

7.6

18.73

22.40

29.11

40

25

8

28.78

34.96

39.17

10.05

60

35

10

31.30

38.10

41.68

12.57

40

15

37.58

45.96

47.96

18.85

45

575-3-60

7.6

6.1

15.83

18.97

24.66

30

20

8

23.87

29.02

32.70

8.04

40

30

10

25.88

31.54

34.71

10.05

30

15

30.91

37.82

39.74

15.08

60

35

ERV

Energy Recovery Ventilator

FLA

Full Load Amps

Hp

Horsepower

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent Protection

NEC

National Electric Code

N/A

Not Applicable

VFD

Variable Frequency Drive

Advertising
This manual is related to the following products: