Carrier 62ME User Manual

Page 53

Advertising
background image

53

Table 3 — Electrical Data With VAV Option (cont)

LEGEND

*The VAV option is not available on 62M040 units.

†Fused disconnect only.

**Exhaust and supply fan motors are 230-3-60.

UNIT SIZE

62M*

VFD

VOLTAGE

V-Ph-Hz

ERV

WHEEL

FLA

VFD

CURRENT

INPUT

VALUE

AMP

EXHAUST AND SUPPLY

FAN MOTOR

HEATER

SIZE
(kW)

POWER SUPPLY

PRE-

HEATER

(Optional)

FLA

DISCONNECT

(Optional)

NEC - FLA

Hp

FLA

MCA

MOCP

Amps

Fuse Size†

Amps

640

208/230-3-60

1.2

26

22

7.5

53.61

65.10

84.64

100

80

8

73.72

90.24 104.74

20.11

200

100

10

78.75

96.52 109.77

25.13

100

15

91.31 112.23 122.33

37.70

110

460-3-60

12.9

11

26.65

32.29

41.98

60

40

8

36.70

44.86

52.03

10.05

50

10

39.21

48.00

54.55

12.57

80

50

15

45.50

55.85

60.83

18.85

60

575-3-60

11.5

9

23.62

28.71

37.33

60

35

8

31.66

38.76

45.37

8.04

45

10

33.67

41.28

47.38

10.05

45

15

38.70

47.56

52.40

15.08

80

50

750

208/230-3-60

2.5

26

22

54.91

65.10

84.64

100

80

10

80.05

96.52 109.77

25.13

200

100

15

92.61 112.23 122.33

37.70

110

20

105.18 127.93 134.90

50.26

125

460-3-60

1.2

12.9

11

27.20

32.29

41.98

60

40

10

39.76

48.00

54.55

12.57

80

50

15

46.05

55.85

60.83

18.85

60

20

52.33

63.71

67.11

25.13

60

575-3-60

1.4

11.5

9

24.50

28.71

37.33

60

35

10

34.55

41.28

47.38

10.05

45

15

39.58

47.56

52.40

15.08

80

50

20

44.61

53.84

57.43

20.11

50

950

208/230-3-60

2.5

34

30.8

10

70.86

85.00 110.50

200

110

10

98.65 119.74 138.29

27.79

125

15

112.55 137.11 152.19

41.69

N/A

20

126.44 154.48 166.08

55.58

N/A

460-3-60

1.2

16.5

14

34.28

41.15

53.49

80

50

10

46.85

56.85

66.06

12.57

60

15

53.13

64.71

72.34

18.85

70

20

59.41

72.56

78.62

25.13

100

70

575-3-60

1.4

14

11

29.63

35.12

45.66

60

45

10

39.68

47.69

55.71

10.05

80

50

15

44.71

53.97

60.74

15.08

60

20

49.73

60.25

65.76

20.11

60

ERV

Energy Recovery Ventilator

FLA

Full Load Amps

Hp

Horsepower

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent Protection

NEC

National Electric Code

N/A

Not Applicable

VFD

Variable Frequency Drive

Advertising