9. circuit analysis, 11. digital section, 16. analog section – Fluke 2180A User Manual

Page 26: Circuit analysis -2, Digital section -2, Analog section -2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2180A

Table 3-1. Mnemonics

ANALOG COM

AZ

CM

DATA

DCLK

DE+

DE-

DIGITAL COM

D.P./NEG

INT 1

LINEAR

WRT

WRT ADR

X10

X100

A 2

+SENSE

-SENSE

+Vm

-V

Measurement common

Auto-Zero

Compare input to the microcomputer

Data on bus

Data clock

Positive read command

Negative read command

—15V with respect to Analog Com

Drives decimal point, depending on reading and resolution

Causes the unknown voltage to be integrated

Used to command the microcomputer to display linear counts

Write

Write address, signals that an address is being transmitted

Selects a buffer gain of X10 (0.1° resolution)

Selects a buffer gain of X100 (0.01° resolution)

Hold command

Voltage sense wires from RTD - no current flows In these wires

Voltage sense wires from RTD - no current flows in these wires

An intermediate voltage - not used directly

Current return

3-9. CIRCUIT ANALYSIS

3-10. Circuit analysis of the 2180A is discussed in two
sections: digital and analog. The digital section is covered
first; particular attention is paid to digital control of the
analog section. The analysis of the analog section covers
the analog measurement circuitry and the 2180A power
supply.

3-11. Digital Section

3-12. The digital section of the 2180A consists of a
single-chip

microcomputer

with

a

self-contained,

programmed, read only memory (U9), a hex CMOS open
drain buffer (U13), and an LED display. This section,
shown in Figure 3-2, will provide the following functions:

1.

Conversion of the non-linear RTD probe

voltage, as measured by the analog section, into a
linear digital display.

2. Control of the analog section.

3. Control of all accessories on the accessory bus.

3-13. The microcomputer (U9) contains all of the 2180 A
programming, control logic, and linearizing capability. It
also provides all signals necessary to update the display.
Linearization of the RTD signal is accomplished by using

a piece-wise, 4th order, curve-fit approximation for each

3-2

type of RTD. One of the seven operating programs is
selected for the RTD type by setting S1 on the RTD Input

Module. A table showing RTD switch setting numbers

and corresponding RTD types is printed on the RTD
Input Module PCB.

3-14. Measurement data is continuously strobed out of
the

microcomputer

in

decoded-seven-segment,

bit-

parallel, character-serial format. This data is then sent to
the LED display.

3-15. The total measurement cycle takes 300 ms. The
cycle consists of the following periods:

1. Auto-Zero period (100 to 200 ms).

2.

Integrate period (100 ms). A 1 ms nominal hold

signal is inserted at the beginning and end of the
Integrate period to accomodate settling times in the
analog section.

3. Read period (variable 0 to 100 ms).

3-16. Analog Section

3-17. ANALOG MEASUREMENT CIRCUIT

3-18. The analog measurement circuitry consists of an
RTD input circuit, two voltage reference circuits, a

ground sense amplifier, a buffer amplifier, a dual slope

Advertising