Table 3 — electrical data, 034 units (cont) – Carrier NP034-074 User Manual

Page 21

Advertising
background image

Table 3 — Electrical Data, 034 Units (cont)

575-3-60 (V-Ph-Hz)

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

BASE UNIT

ONLY

EXHAUST

FAN

ELECTRIC

HEAT*

BASE UNIT WITH

EXHAUST FAN

AND/OR

ELECTRIC HEAT*

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

MCA

MOCP

Total

Hp

Total

FLA

kW

FLA

MCA

MOCP

518-632

23.1

96.0

23.1

96.0

4.8

7.5

9.0

65.8

80

6.0

7.8

73.6

90

10.0

12.2

78.0

100

15.0

18.0

83.8

100

36

36.0

65.8

80

72

72.0

101.3

110

108†

108.0

146.2

150

6.0

7.8

36

36.0

73.6

90

6.0

7.8

72

72.0

101.3

110

6.0

7.8

108†

108.0

146.2

150

10.0

12.2

36

36.0

78.0

100

10.0

12.2

72

72.0

101.3

110

10.0

12.2

108†

108.0

146.2

150

15.0

18.0

36

36.0

83.8

100

15.0

18.0

72

72.0

101.3

110

15.0

18.0

108†

108.0

146.2

150

10.0

11.0

67.8

90

6.0

7.8

75.6

90

10.0

12.2

80.0

100

15.0

18.0

85.8

100

36

36.0

67.8

90

72

72.0

103.7

110

108†

108.0

148.7

150

6.0

7.8

36

36.0

75.6

90

6.0

7.8

72

72.0

103.7

110

6.0

7.8

108†

108.0

148.7

150

10.0

12.2

36

36.0

80.0

100

10.0

12.2

72

72.0

103.7

110

10.0

12.2

108†

108.0

148.7

150

15.0

18.0

36

36.0

85.8

100

15.0

18.0

72

72.0

103.7

110

15.0

18.0

108†

108.0

148.7

150

15.0

17.0

73.8

90

6.0

7.8

81.6

100

10.0

12.2

86.0

100

15.0

18.0

91.8

110

36

36.0

73.8

100

72

72.0

111.2

125

108†

108.0

156.2

175

6.0

7.8

36

36.0

81.6

100

6.0

7.8

72

72.0

111.2

125

6.0

7.8

108†

108.0

156.2

175

10.0

12.2

36

36.0

86.0

100

10.0

12.2

72

72.0

111.2

125

10.0

12.2

108†

108.0

156.2

175

15.0

18.0

36

36.0

91.8

110

15.0

18.0

72

72.0

111.2

125

15.0

18.0

108†

108.0

156.2

175

20.0

22.0

78.8

100

6.0

7.8

86.6

100

10.0

12.2

91.0

110

15.0

18.0

96.8

110

36

36.0

78.8

110

72

72.0

117.5

150

108†

108.0

162.5

175

6.0

7.8

36

36.0

86.6

110

6.0

7.8

72

72.0

117.5

150

6.0

7.8

108†

108.0

162.5

175

10.0

12.2

36

36.0

91.0

110

10.0

12.2

72

72.0

117.5

150

10.0

12.2

108†

108.0

162.5

175

15.0

18.0

36

36.0

96.8

110

15.0

18.0

72

72.0

117.5

150

15.0

18.0

108†

108.0

162.5

175

LEGEND

CV

Constant Volume

ETL

ETL Testing Laboratory

FLA

Full Load Amps

Hp

Nominal Horsepower

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Electric heat available on 50 Series vertical discharge units.

†108 kW available on CV applications only.

NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To

determine heater capacity (kW) at unit operating voltage, multiply 240 v,
480 v, or 575 v capacity by appropriate multiplier below.

MULTIPLICATION FACTORS

HEATER kW

RATING

VOLTAGE

DISTRIBUTION

V-3-60

MULTIPLICATION

FACTOR

240

200
208
230
240

0.694
0.751
0.918
1.000

480

440
460
480

0.840
0.918
1.000

575

550
575
600

0.915
1.000
1.089

Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.

2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series