Condenser fans and motors, Return-air filters, Economizer inlet screens – Carrier NP034-074 User Manual

Page 40: Economizer dampers, 25% outdoor-air damper

Advertising
background image

Table 9B — Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units

IFM

Hp

IFM

RPM

MOTOR PULLEY

BLOWER PULLEY

BELTS

48 Series and 50 Series

Horizontal Discharge Units

50 Series

Vertical Discharge Units

No.

Grooves

Type

Size (in.)

No.

Grooves

Type

Size (in.)

Quantity

Type

Size (in.)

Quantity

Type

Size (in.)

15

450

2

B5V

4.3

2

B5V

18.5

2

5VX

118

2

5VX

132

470

16.1

115

125

485

15.5

123

575

4.5

13.7

112

650

5.1

725

5.7

20

405

3

B5V

4.3

3

B5V

18.5

3

5VX

123

3

5VX

132

470

16.1

118

125

485

15.5

575

2

4.5

2

13.7

2

115

2

123

660

5.1

725

5.7

25

405

3

B5V

4.3

3

B5V

18.5

3

5VX

123

3

5VX

132

470

16.1

115

125

485

15.5

123

575

2

4.5

2

13.7

2

B5V

2

700

5.5

725

5.7

30

470

4

B5V

4.3

4

B5V

16.1

4

5VX

118

4

5VX

123

485

15.5

530

3

4.7

3

15.5

3

3

600

2

5.5

2

15.5

2

2

660

5.9

730

6.5

IFM — Indoor (Evaporator) Fan Motor

Check rotation of wheel with arrow on the fan housing.

Check fan speed with a strobe-type tachometer, or use this
formula:

motor rpm x motor sheave pitch diameter (in.)

Fan

=

Rpm

fan sheave pitch diameter (in.)

(Obtain motor rpm from the fan motor nameplate and read

sheave pitch diameters marked on the fan and motor sheaves.)

Example:
Nameplate motor rpm .................................................. 1760
Motor sheave pitch diameter (in.) .................................. 6.4
Fan sheave pitch diameter (in.) .................................... 12.4

1760 x 6.4

Fan Rpm =

= 908 Rpm

12.4

The maximum allowable fan speed for the supply-air fan

is 900 rpm for 034 and 044 units and 750 rpm for 054-074
units. The maximum rpm for the power exhaust is 1300 rpm
for 034 and 044 units and 925 rpm for 054-074 units.
Excessive fan speed may result in condensate carryover from
the evaporator coil, fan motor overload, or wheel failure. See
Table 10 for Air Quantity Limits.

Table 10 — Air Quantity Limits (cfm)

UNIT SIZE

MINIMUM

MAXIMUM

034

6,000

15,000

044

8,000

20,000

054

10,000

25,000

064

12,000

30,000

074

14,000

30,000

Condenser Fans and Motors —

Each unit has mul-

tiple condenser fans and motors; these are positioned at the
factory. See Fig. 32 for correct location of fan in orifice. Check
that fan propeller rotation is correct; it should be counter-
clockwise when facing the fans. If fan propeller rotation is
incorrect, switch motor leads.

Return-Air Filters —

Check that the correct filters are

installed in the filter rack. See Tables 1A and 1B for quan-
tities and sizes. Access is through the door marked FILTER
SECTION. Do not operate the unit without return-air filters.

Economizer Inlet Screens —

Check that they are in

place before operating the unit.

Economizer Dampers —

With no power to the unit,

the economizer outdoor-air dampers should be fully closed.
Check by opening the access door marked FILTER SEC-
TION. On units with economizer, be sure economizer mini-
mum position is set at the desired setting. Be sure hood is
installed properly.

25% Outdoor-Air Damper —

On units without econo-

mizer, be sure 25% outdoor-air damper is set at the desired
position. Also, be sure hood is installed properly.

40