Operating instructions – ebm-papst A3G800-AN36-23 User Manual

Page 8

Advertising
background image

Operating instructions

A3G800-AN36-23

Translation of the original operating instructions

Fig. 2: Connecting the wires to terminals
; Seal the terminal box.

4.3.3 Cable routing

No water may penetrate along the cable in the direction of the cable gland.

Fans installed lying flat
Make sure that the cable is routed in the form of a loop (water trap).

Fig. 3: Fan installed lying flat, cable routed as a water trap.

Fans installed in upright position
When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 4: Cable routing for fans installed upright.

4.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Operation mode

PWM controlling

Group adress

1

Fan / device adress

1

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

No

Set value control

Analog

Control function

Positive (heating)

Item no. 50443-5-9970 · ENG · Revision 84593 · Release 2015-01-05 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Advertising