4.5 Connection screen

No.

Conn.

Designation

Function / assignment

PE

PE

Protective earth

KL1

N

Mains 50/60 Hz, neutral

KL1

L

Mains 50/60 Hz, phase

KL2

COM

Alarm relay, COMMON (2A, 250 VAC, AC1)

KL2

NC

Alarm relay, normally closed connection

KL2

NO

Alarm relay, close with error

KL3

+10 V

Supply for external potentiometer, 10 VDC (+10%) @ 10 mA

KL3

+20 V

Supply for external sensor, 20 VDC (±20%) @ 50 mA

KL3

0-10 V/PWM

Control / Actual sensor value input

KL3

0-10 V/PWM

Control / Actual sensor value input (impedance 100 kΩ)

KL3

4-20 mA

Control / Actual sensor value input

KL3

GND

GND

KL3

GND

GND

KL3

OUT

Master output 0-10 V max. 3 mA

KL3

RSA

RS485 interface for ebmBUS; RS A

KL3

RSA

RS485 interface for ebmBUS; RS A

KL3

RSB

RS485 interface for ebmBUS; RS B

KL3

RSB

RS485 interface for ebmBUS; RS B

Item no. 50443-5-9970 · ENG · Revision 84593 · Release 2015-01-05 · Page 9 / 12