5.

Press and release the START/STOP key (1): the test to verify the correct insertion of the needle probe will be

started; see paragraph 6.14 " Test for verification of the correct insertion of the needle probe".

5.1

If the test is completed successfully, the cycle will be started.

The maximum blast chilling duration count is started on condition that the temperature detected by the

needle probe is below that established with parameter r15.

5.2

If the test is not completed successfully, the buzzer will be activated for 5 s every 60 s and the cycle will

be started with timed-control; see paragraph 6.4 "Time-controlled hard blast chilling and storage".

During hard blast chilling phase the device displays the temperature detected by the needle probe, the cabinet

temperature, the program name (if envisioned) and the time passed since the start of blast chilling .

Operate as indicated to stop the cycle:

6.

Press and hold the START/STOP key 3 s.

The successive parameters establish the following values:

-

parameter r5 establishes the maximum blast chilling duration

-

parameter r9 establishes the work set-point during the blast chilling hard phase

-

parameter r13 establishes blast chilling hard phase end temperature.

When the temperature detected by the needle probe reaches the hard blast chilling phase end temperature, the device

automatically passes to blast chilling mode.

During blast chilling the device displays the temperature detected by the needle probe, the cabinet temperature, the

program name (if envisioned) and the time passed since the start of blast chilling.

The successive parameters establish the following values:

-

parameter r3 establishes the blast chilling end temperature

-

parameter r5 establishes the maximum blast chilling duration

-

parameter r7 establishes the work set-point during blast chilling.

If the temperature detected by the needle probe reaches the blast chilling end temperature within the maximum blast

chilling duration, it means that blast chilling has been completed successfully, the device will automatically pass to

storage and the buzzer will be activated for the period of time established with parameter AA.

Press and release a key to silence the buzzer.

During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the time

taken to complete blast chilling successfully.