2 list of installer menu configuration parameters – EVCO c-pro CLIMA sistema Installer manual User Manual

Page 56

Advertising
background image

C-PRO CLIMA SISTEMA INSTALLER MANUAL

Page 56

Booster Parameters
Booster H

Zone assignment (of the associated MCZN regulator)
to which the heating integration Hot Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B

ZA+ZB

---

ZA+ZB

Booster Parameters
Booster C

Zone assignment (of the associated MCZN regulator)
to which the cooling integration Cold Booster function
is associated:
- --- = no Zone associated
- ZA = associated to Zone A
- ZB = associated to Zone B
- ZA+ZB associated to Zone A and Zone B

ZA+ZB

---

ZA+ZB

Booster Parameters
Set deh1 in

Minimum input temperature dehumidifier 1 setpoint
for enabling of Heating Booster
(expressed in °C)

35.0

0.0

100.0

Booster Parameters
Set deh2 in

Minimum input temperature dehumidifier 2 setpoint
for enabling of Heating Booster
(expressed in °C)

35.0

0.0

100.0

Booster Parameters
Dehum. activ.

Link between the activation of the booster output and
the activation of the dehumidifier output

Yes

No

Yes

CO2

CO2 parameters
Enable reg.

Enabling regulation of the CO2 level

Yes

No

Yes

CO2 parameters
Dumper mode

Fresh air dumper functioning mode:
- --- = not enabled
- CLOSED = fixed
- MODUL. = modulating
- OPEN = fixed

MODUL.

---

OPEN

CO2 parameters
Setpoint

Room maximum CO2 level setpoint due to dumper
opening
(expressed in parts per million)

0

0

2000

CO2 regulation
Hysteresis

Hysteresis (differential) relative to the CO2 setpoint
(expressed in parts per million)

10

0

100

7.7.2

List of INSTALLER menu configuration parameters


Label

Parameter description

Default

Min

Max

I/O CONFIGURATION

I/O configuration
AIn3

AIn3 analogue input configuration type:
- 4-20mA
- 0-5V

4-20mA

4-20mA

0-5V

I/O configuration
DIn

Type of contact for digital inputs
NA = normally open
NC = normally closed

N.O.

N.C.

N.O.

GENERAL PARAMETERS

General parameters
MCZN assigned

MCZN zone regulator to which the MCDE module is
associated

1

1

8

General parameters
CANBUS address

CANbus serial address

0

0

255

General parameters
Baud Rate

CANbus communication speed (baud rate)
-20Kbit
-50Kbit
-125Kbit
-500Kbit

125Kbit

20Kbit

500Kbit

Advertising