2.6

Preset configurations


The controller preset configurations are reported below.

2.6.1

C-PRO MEGA RACK preset configurations (single circuit compressor packs)

Analogue inputs

Digital outputs

Digital inputs

Suction probe

4 Compressors

4 compressor thermals

Supply probe

3 Fans

Fan thermal common connections

1 global alarm relay

Fluid level

Low pressure pressure-switch

High pressure pressure-switch

Input/output configuration

Terminal

Analogue input

Description

AI1

No. 1 analogue input (4..20 mA)

Suction probe

AI2

No. 2 analogue input (4..20 mA)

Supply probe

Terminal

Analogue output

Description

By default – not configured

Terminal

Digital input

Description

DI1

No. 1 digital input

Compressor 1 thermal

DI2

No. 2 digital input

Compressor 2 thermal

DI3

No. 3 digital input

Compressor 3 thermal

DI4

No. 4 digital input

Compressor 4 thermal

DI5

No. 5 digital input

Fan thermal common connection

DI6

No. 6 digital input

Fluid level

DI7

No. 7 digital input

Low pressure (suction) pressure-switch

DI8

No. 8 digital input

High pressure (supply) pressure-switch

Terminal

Digital output

Description

DO1

No. 1 digital output

Compressor 1

DO2

No. 2 digital output

Global alarm relay

DO3

No. 3 digital output

Compressor 2

DO4

No. 4 digital output

Compressor 3

DO5

No. 5 digital output

Compressor 4

DO6

No. 6 digital output

Fan 1

DO7

No. 7 digital output

Fan 2

DO8

No. 8 digital output

Fan 3