C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL

Page

53

alarm diff.

pressure alarm differential

> 1

PA27

Circuit 2 suction
HP alarm
setpoint .

Circuit 2 suction probe high
pressure alarm setpoint

4.0

PA25

PH02

Bar

IS-S

Visible if PG01
> 1

PA28

C2 suction HP
alarm diff.

Circuit 2 suction probe high
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

Visible if PG01
> 1

PA29

C2 supply LP
alarm setpoint

Circuit 2 supply probe low
pressure alarm setpoint

2.0

PH03

PA31

Bar

IS-S

Visible if PG01
> 1 and PG30 =
0

PA30

C2 supply LP
alarm diff.

Circuit 2 supply probe low
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

Visible if PG01
> 1 and PG30 =
0

PA31

C2 supply HP
alarm setpoint

Circuit 2 supply probe high
pressure alarm setpoint

20.0

PA29

PH04

Bar

IS-S

Visible if PG01
> 1 and PG30 =
0

PA32

Circuit 2 supply
HP alarm diff.
.

Circuit 2 supply probe high
pressure alarm differential

1.0

0.0

20.0

Bar

IS-S

Visible if PG01
> 1 and PG30 =
0

PA35

C3 suction LP
alarm setpoint

Circuit 3 suction probe low
pressure alarm setpoint

0.5

PH01

PA37

Bar

IS-S

Visible if PG01
> 2

PA36

C3 suction LP
alarm diff.

Circuit 3 suction probe low
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

Visible if PG01
> 2

PA37

C3 suction HP
alarm setpoint

Circuit 3 suction probe high
pressure alarm setpoint

4.0

PA35

PH02

Bar

IS-S

Visible if PG01
> 2

PA38

C3 suction HP
alarm diff.

Circuit 3 suction probe high
pressure alarm differential

0.5

0.0

20.0

Bar

IS-S

Visible if PG01
> 2