Connector 3: Connector for the analogue output (optional, not available in the day versions)

Conn.

Code

Description (Version V+I)

C3-1

AO2

0-10VDC

C3-2

GND

Common analogue output

C3-3

AO3

4-20mA

Description (Version I+I)

C3-1

AO2

4-20mA

C3-2

GND

Common analogue output

C3-3

AO3

4-20mA

Description (Version V+V)

C3-1

AO2

0-10VDC

C3-2

GND

Common analogue output

C3-3

AO3

0-10Vdc


Connector 4: Connector for low voltage signals

Conn.

Code

Description

C4-1

12VAC

Power supply (12VAC/DC)

C4-2

5V

Ratiometric transducers power supply

C4-3

GND

Common analogue and digital inputs

C4-4

GND

Common analogue and digital inputs

C4-5

AI4

Analogue input n.4
(for NTC probes, 0/4-20 mA or 0-5V transducers)

C4-6

AI3

Analogue input n.3
(for NTC probes, 0/4-20 mA or 0-5V transducers)

C4-7

AI2

Analogue input n.2 (for NTC probes)

C4-8

AI1

Analogue input n.1 (for NTC probes)

C4-9

12VAC

Power supply (12VAC/DC)
(max. 50 mA, not protected against short circuit)

C4-10

12VDC

0/4-20 mA transducers and phase cut module power supply

C4-11

AO1

Jog output for phase cut module

C4-12

DI5

Digital input n.5

C4-13

DI4

Digital input n.4

C4-14

DI3

Digital input n.3

C4-15

DI2

Digital input n.2

C4-16

DI1

Digital input n.1


Connector 5: Connector for the remote keyboard and expansion of I/O (CAN)

Conn.

Code

Description

C5-1

CAN +

Connector for the connection of the CAN + serial port

C5-2

GND

Ground reference connector

C5-3

CAN -

Connector for the connection of the CAN - serial port