C-PRO MICRO SAVE APPLICATION MANUAL

Page 32

Code

Parameter description

Default

Min

Max

UM

Menu

Notes

ALARM PARAMETERS

PA03

Enabling of outlet/return fans thermal switch
alarm

Active

(1)

Not-

active (0)

Active

(1)

-

CO-S

PA05

Enabling of differential pressure switch alarm

Active

(1)

Not-

active (0)

Active

(1)

Sec

CO-S

PA06

Delay of differential pressure switch alarm

10

0

999

Sec

CO-S

PA08

Signals differential pressure switch alarm on
alarm relay

Yes (1)

No (0)

Yes (1)

Sec

CO-S

Only if
PG02=0

PA09

Anti-freeze alarm active on hot water coil

Not-

active (0)

Not-

active (0)

Active

(1)

Sec

CO-S

PA10

Anti-freeze alarm delay on hot water coil

10

0

999

Sec

CO-S

PA12

Activates the heaters thermal overload alarm

Active

(1)

Not-

active (0)

Active

(1)

Sec

CO-S

Only if
PG02=1

PA13

Signals heaters thermal switch alarm on alarm
relay

Yes (1)

No (0)

Yes (1)

CO-S

Only if
PG02=1

PA16

Enable supply high temperature alarm from
temperature probe

Active

(1)

Not-

active (0)

Active

(1)

CO-S

PA17

Supply high temperature alarm setpoint

85.0

PH01

PH02

°C

°F

CO-S

PA19

Supply high/low temperature alarms
differential

3.0

0.0
0.0

20.0
36.0

°C

°F

CO-S

PA20

High/low temperature alarms delay

10

0

999

Sec

CO-S

PA22

Expansion alarm delay

5

0

999

Sec

CO-S

PA24

RTC alarm enabling

Active

(1)

Not-

active (0)

Active

(1)

-

CO-S

PA26

Probes alarms signals delay

10

0

240

Sec

CO-S

VARIOUS PARAMETERS

PH11

Board Modbus address

1

1

247

-

CO-V

PH12

Communication Baud Rate for the board
(0=1200, 1=2400, 2=4800, 3=9600, 4=19200)

3

0

4

-

CO-V

PH13

ModBus Parity (0=none, 1=Odd, 2=Even)

2

0

2

-

CO-V

PH14

Stop Bit ModBus (0=1bit, 1=2bit)

0

0

1

-

CO-V

PH40

Enable outlet temperature probe

Yes (1)

No (0)

Yes (1)

-

CO-V

PH41

Enable return temperature probe

Yes (1)

No (0)

Yes (1)

-

CO-V

PH42

Enable CO

2

probe (0-5V)

No (0)

No (0)

Yes (1)

-

CO-V

PH43

Enable outside air temperature probe

Yes (1)

No (0)

Yes (1)

-

CO-V

PH51

Logic of the digital input DI1

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH52

Logic of the digital input DI2

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH53

Logic of the digital input DI3

N.C. (1)

N.O. (0)

N.C. (1)

-

CO-V

PH54

Logic of the digital input DI4

N.C. (1)

N.O. (0)

N.C. (1)

-

CO-V

PH55

Logic of the digital input DI5

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH56

Logic of the digital input DI6

N.C. (1)

N.O. (0)

N.C. (1)

-

CO-V

PH57

Logic of the digital input DI7

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH58

Logic of the digital input DI8

N.C. (1)

N.O. (0)

N.C. (1)

-

CO-V

PH59

Logic of the digital input DI9

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH60

Logic of the alarm relay DO10

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH61

Logic of the alarm relay DO12

N.O. (0)

N.O. (0)

N.C. (1)

-

CO-V

PH80

CAN communication Baud Rate
(20K, 50K, 125K, 500K)

1

1

4

-

CO-V

Notes:The outside air return probes activation parameters, respectively PH41 and PH43 are conditioned by the state of
the digital input that indicates the presence of the By-Pass damper (DI5). If the input confirms the presence of the By-
Pass, the two parameters are active, otherwise they are deactivated. Any changes to the parameters are allowed, but any
change in state of the digital input DI5 implies changes of the two parameters.

Once the machine parameters have been configured and at every modification of the configuration parameters, it is
advised to remove and re-apply the power supply to the board to allow the control to configure itself correctly.