- 10 -

Figure 6 Distribution Box

4. Network Connection: The Ethernet connection at JP1 is an RJ-45 style jack. A 10 foot

Ethernet Cat 5 crossover cable is supplied with the unit.

B.

Distribution Box (see Figure 6)

1. Connect the RS-485 wires (blue, white and shield) and 24Vdc power (red and black) from

the main processor unit.

2. Install ½” liquid-tight conduit between the distribution enclosure and the probes unless ½”

rigid conduit is used for long distance runs. Use a minimum of 6 feet of liquid tight at the
probes.

3. The probe connector comes with an adapter which allows the attachment of the ½” flexible

conduit connector.

4. Connect the probes to the distribution enclosure using the manufacturer supplied four

conductor shielded cable. Probe cable connections are shown in Figure 6.

5. Optional - Connect the transmitter box to the distribution box using a RS-485 cable.