Interlogix NX-588E User Manual

Page 3

Advertising
background image

NX-588E USB Flash Programmer Installation Instructions

3

1

Command

—read panel configuration into a file.

2

Command

—w rite a file configuration into the panel.

10

Result

—w orking.

11

Result

—invalid command; installer entered a value other than

1 or 2.

12

Result

—invalid file number; installer entered a file number

other than 1 to 4.

13

Result

—incorrect panel type; the panel and file types do not

match.

14

Result

—incorrect access code; the panel and file access code

do not match.

15

Result

—timeout; the requested command had no data

exchange for 3 seconds.

16

Result

—aborted; the previous command w as aborted by

attempting another command.

17

Result

—panel type not supported.

18

Result

—panel type not loaded from bus (retry).

20

Result

—transfer successful; the previous read or write

command w as successful.

The DS5 LED flashes as the system runs the command.

Once the command is successful, the keypad chimes. For

LED locations, refer to Figure 1 below, and for LED

descriptions, refer to Table 2 below.

8. To write (copy a file from the NX-588E to the NX panel),

do the following:

Enter 2, *.

Enter the number of the file to copy (1 to 4)*, #.

The DS5 LED flashes as the system runs the command. Once

the command is successful the keypad sounder chimes.

Note: A triple-beep sounds if any error occurs during step 7 or

step 8. You can review the results in t

he “Reviewing segments

and tasks for location 0

” below

.

Figure 1: LED locations

Table 2: LED descriptions

LED

Description

DS1

Bus action

Flashes when connected to NetworX bus

DS2

USB

Off = no USB

Flashes = in progress

Steady = USB attached

DS3

Receiving USB

DS4

Sending USB

DS5

Waiting for bus response

DS6

Programming/error

Flashes slow ly (once per second) = programming in

progress

Flashes rapidly (three times per second) = error

Steady = programming successful

Reviewing segments and tasks for location 0

The only location you will use on the NX-588E is Location 0.

The seven segments have the following functions:

Segment 1

Sets the task to perform (read or write) and displays the result

of the task requested (see Table 1 on page 2).

Segment 2

This stores the file number for the requested read or write

command, a valid value between 1 and 4. This segment is
always set to 0 after any command, so you don’t accidentally
overwrite a file.

Segments 3 through 6

Indicates the panel type stored in files 1 through 4 respectively.

The results include the following:

0 to 3 applies to the standard NetworX panels (NX-4, NX-

6, NX-8)

4 applies to the NX-8E panel

10 applies to the NX-4V2 panel

11 applies to the NX-6V2 panel

12 applies to the NX-8V2 panel

Segment 7.

Not used.

Upgrading the NX-4V2, NX-6V2, NX-8V2

When upgrading a control panel, all auxiliary outputs will

deenergize. Do not be concerned with any sound that comes