E s l, 06 dpdt relay module, 4300 series wireless smoke alarm – Interlogix ESL 500 Series User Manual

Page 2: Installation instructions

Advertising
background image

4300 Series

Wireless Smoke Alarm

.

Installation Instructions

1. Connect 405-06 trip wires to trigger circuit. Observe

polarity. [Gray to positive (+) and White to negative (-)].

2. Connect the 405-06 DPDT relay contacts as required.

The first set of contacts are:

common

red

closed

white-red

open

white-blue

3. The second set of contacts are:

common

black

closed

white-black

open

blue

4. When fail safe operation is required, wire the relay in the

powered or energized condition.

5. Do not exceed rating of relay.
6. Testing: 405-06

Test unit in accordance with NFPA 72 Chapter 7 Test

Methods and Frequencies, interface equipment.
To test the 405-06, energize the relay coil and confirm the

contacts tranfer.

Specifications for 405-05 & 405-06

Operating voltage..........................................................8.5-33VDC

Maximum operating current............................34.0 mA at 12 VDC

35.0 mA at 24 VDC

Relay contacts ............................ 2 A at 30 VDC, 1 A at 120 VAC

Operating temperature .................32° F to 120° F (0° C to 49° C)

Operating humidity range .................0 to 85% Non-condensing

Dimensions ..................................1.8 in. (4.6 cm) x 1.7 in. (4.3 cm)

Wire connections ............... 18 AWG stranded, tinned, 18” long

405-06
DPDT Relay Module

For use as a Universal Switch Device

Sentrol-Caddx reser ves the right

to change specifications

without notice.

©2000 Sentrol-Caddx

12345 SW Leveton Dr., Tualatin, OR 97062

Tel.: 503.692.4052 Fax: 503.691.7566

http://www.sentrol.com

U.S. & Canada: 800.547.2556
Technical Service: 800.648.7424
FaxBack: 1.800.483.2495

SENTROL-CADDX

E S L

a p r o d u c t o f s e n t r o l

12859 Rev B 07/00

-

W

hite

+

Gray

NC

NC

COM

NO

COM

NO

White-Red

Red

White-Blue

White-Black

Black

Blue

ESL 405-06
DPDT Relay