Single Point Boxes and Supplementary Fuse

When the unit MOCP device value exceeds 60--A,

unit--mounted supplementary fuses are required for each

heater circuit. These fuses are included in accessory

Single Point Boxes, with power distribution and fuse

blocks. The single point box will be installed directly

under the unit control box, just to the left of the partition

separating the indoor section (with electric heaters) from

the outdoor section. The Single Point Box has a hinged

access cover. See Fig. 26. The Single Point Box also

includes pigtails to complete the wiring between the

Single Point Box and the unit’s main control box

terminals. Refer to the accessory heater and Single Point

Box installation instructions for details on tap

connections.

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

11

13

21

23

OD

22.2

3

1

23

ISTED AIR

NDITIONING

UIP ACCESS
346N.

P / N

2-

5610-4

REV

1

1

13

2

1

2

3

CONTROL
BOX

BUSHING

SINGLE
POINT BOX
MOUNTING
SCREWS

FOAM
BUSHING

DRIP BOOT
BRACKET
MOUNTING
SCREWS

HEATER
RELAYS

POWER
WIRES

HEATER
MOUNTING
SCREWS

C08136

Fig. 26 -- Typical Single Point Installation

All fuses on 50HCQ units are 60--A. (Note that all heaters

are qualified for use with a 60--A fuse, regardless of actual

heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses: Refer to accessory

heater and Single Point Box installation instructions for

details on tap connections.
Low--Voltage Control Connections: Run the low--voltage

control leads from the heater module(s) -- VIO and BRN

(two of each if two modules are installed; identify for

Module #1) -- to the 4--pole terminal board TB4 located on

the heater bulkhead to the left of Heater #1. Connect the

VIO leads from Heater #1 and Heater #2 to terminal

TB4--1. Connect the BRN leads to terminal TB4--3. See

Fig. 27.

DEFROST

BOARD

ORN

BRN

Field
Connections

E-HEAT

P3-3

1

3

ORN

BRN

VIO

BRN BRN

VIO

TB4

VIO

HR2

HR1

BRN

VIO

BRN

Elec Htr

HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)

C09013

Fig. 27 -- Accessory Electric Heater Control Connections

50H

C

Q

A

Advertising