Carrier 50HCQA User Manual

Page 23

Advertising
background image

23

8 7 6 5 4 3 2 1

2 1

H G 24 VAC

OR

24 VDC

NC

ALARM
RELAY
CONTACTS

COM
NO

}

0-10VDC
SIG COM

4-20mA

+

+

-

+ -

J3

J4

C08635

Fig. 38 -- Indoor/Outdoor Air Quality (CO

2

) Sensor

(33ZCSENCO2) -- Typical Wiring Diagram

To accurately monitor the quality of the air in the

conditioned air space, locate the sensor near a return--air

grille (if present) so it senses the concentration of CO

2

leaving the space. The sensor should be mounted in a

location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near

supply ducts, open windows, fans, or over heat sources.

Allow at least 3 ft (0.9 m) between the sensor and any

corner. Avoid mounting the sensor where it is influenced

by the supply air; the sensor gives inaccurate readings if

the supply air is blown directly onto the sensor or if the

supply air does not have a chance to mix with the room air

before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor: For each sensor,

use two 2--conductor 18 AWG (American Wire Gage)

twisted--pair cables (unshielded) to connect the separate

isolated 24 vac power source to the sensor and to connect

the sensor to the control board terminals.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

sensor. See Fig. 38. Connect the 4--20 mA terminal to

terminal TB1--9 and connect the SIG COM terminal to

terminal TB1--11. See Fig. 39.

SEN

J5-5

J5-3

COM

9

11

TB1

TB1

IAQ Sensor

PL

24 VAC

C08636

Fig. 39 -- Indoor CO

2

Sensor (33ZCSENCO2)

Connections

Refer to Form 33CS--58SI, PremierLink Installation,

Start--up, and Configuration Instructions, for detailed

configuration information

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —

The outdoor air CO

2

sensor is designed to monitor carbon

dioxide (CO

2

) levels in the outside ventilation air and

interface with the ventilation damper in an HVAC system.

The OAQ sensor is packaged with an outdoor cover. See

Fig. 40. The outdoor air CO

2

sensor must be located in the

economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 40 -- Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO

2

Sensor: A dedicated

power supply is required for this sensor. A two--wire cable

is required to wire the dedicated power supply for the

sensor. The two wires should be connected to the power

supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 38. Connect the 4 to 20 mA

terminal to the TB1--13 terminal of the 50HCQ. Connect

the SIG COM terminal to the TB1--11 terminal of the

50HCQA. See Fig. 41.

SEN

J5-2

J5-3

COM

13

11

TB1

TB1

PL

OAQ Sensor/RH Sensor

24 VAC

C08275

Fig. 41 -- Outdoor CO

2

Sensor Connections

Smoke Detector/Fire Shutdown (FSD) —

This function is available only when PremierLink is

configured for (Space) Sensor Mode. The unit is

factory--wired for PremierLink FSD operation when

PremierLink is factory--installed.

50H

C

Q

A

Advertising