Table 2 — 19XR Dimensions (Marine Waterbox)

HEAT EXCHANGER

SIZE

A (Length, Marine Waterbox —

not shown)

2-Pass*

1 or 3 Pass†

ft-in.

mm

ft-in.

mm

10 to 12

NA

NA

NA

NA

15 to 17

NA

NA

NA

NA

20 to 22

12- 6

5

8

3826

14- 3

4343

30 to 32

14- 9

4496

16- 4

3

4

4997

35 to 37

16- 5

1

2

5017

18- 1

1

4

5518

40 to 42

15- 0

1

4

4591

16- 8

3

4

5099

45 to 47

16- 8

3

4

5099

18- 5

1

4

5620

50 to 52

15- 0

1

4

4591

16- 8

3

4

5099

55 to 57

16- 8

3

4

5099

18- 5

1

4

5620

60 to 62

15- 0

3

4

4591

16- 9

1

4

5111

65 to 67

16- 9

1

4

5112

18- 5

3

4

5632

70 to 72

17- 8

5385

19-10

1

2

6058

75 to 77

19- 8

5994

21-10

1

2

6668

80 to 82

17- 8

1

2

5398

20- 1

6121

85 to 87

19- 8

1

2

6007

22- 1

6731

*Assumes both cooler and condenser nozzles on same end of chiller.

†1 or 3 pass length applies if cooler is a 1 or 3 pass design.

NOTES:
1. Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition,

National Fire Protection Association (NFPA) 70, and local safety code.

2. Allow at least 3 ft (915 mm) overhead clearance for service rigging.
3. Certified drawings available upon request.

Table 3 — 19XR Nozzle Size

FRAME

SIZE

NOZZLE SIZE (in.)

(Nominal Pipe Size)

Cooler

Condenser

1-Pass

2-Pass

3-Pass

1-Pass

2-Pass

3-Pass

1

8

6

6

8

6

6

2

10

8

6

10

8

6

3

10

8

6

10

8

6

4

10

8

6

10

8

6

5

10

8

6

10

10

8

6

10

10

8

10

10

8

7

14

12

10

14

12

12

8

14

14

12

14

14

12

8