DC Power Connections
Step 4
Connect the DC power lead from the first external power source to the DC terminal block A labeled –48V.
Step 5
Connect the return wire (RTN) to terminal block A labeled RTN (+).
•
If you have redundant DC power, continue with Step 6.
•
If you do not have redundant DC power, go to Step 8.
Step 6
Connect the DC power lead from the second external power source to the DC terminal block B labeled –48V.
Step 7
Connect the return wire (RTN) to terminal block B labeled RTN (+).
30024
RTN (+)
DC terminal
block B
– 48/–60
V
RTN (+)
– 48/–60
V
DC terminal
block A