Press the up

key to begin calibrating.

The controller displays the name of the current calibration
(examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC.H).

Wait until the control displays “don” or “bad.”

A “don” message in the Setpoint display indicates the cali-
bration was successful. A “bad” message in the Setpoint
display indicates a bad calibration.

Press Select to start the next calibration.

Pressing and releasing the Select key at the end of a
calibration tells the controller to perform the next calibra-
tion.

Exit Calibration Mode.

Press and hold the Select key for 3 seconds to exit the
Calibration Mode.

You can now proceed to the next test in Test Mode, or
disable Test Mode and resume normal operation.

C

ALIBRATING

T

EMPERATURE

S

ENSORS

UGH004/0999

microKool Portable Chillers

M

AINTENANCE

5-13

6

7

NOTE: The original calibration value stored in
EEProm can be restored for the current calibration
by pressing the STOP key at any time.

8

TO DISABLE TEST MODE, complete steps 2
through 5 in

P

ERFORMING

S

YSTEM

T

ESTS

, setting dip

switch 6 to OFF instead of ON.

9