PECIFICATIONS

: MPA (A

IR

C

OOLED

)

UGH004/0999

microKool Portable Chillers

D

ESCRIPTION

2-7

MODEL

MPA-1.5

MPA-2

MPA-3

MPA-4

MPA-5

MPA-7.5

MPA-11

Performance characteristics

Capacity {tons} *

1.2

1.7

2.7

3.5

4.1

6.9

10.2

Compressor Hp {kW}

1.5 {1.12}

2.25 {2.05}

3.25 { 279.7}

4 {2.98}

5 {3.73}

9 {6.71}

12 {8.95}

Pump Hp (kW)†

0.33 {0.246}

0.50 {0.373}

0.75 {0.559}

1.5 {1.12}

1.5 {1.12}

1.5 {1.12}

1.5 {1.12}

Chilled water flow gpm {l/min}‡

2.8 {10.6}

4.2 {15.9}

6.4 {24.2}

8.5{32.1}

9.9 {37.5}

16.6 {62.8}

24.5 {92.7}

Chilled water pressure psi {bar}§

20 {1.4}

26 {1.8}

34 {2.3}

38 {2.6}

38 {2.6}

37.5 {2.6}

37 {2.5}

Reservoir capacity gal {l}

10 {37.9}

30 {114}

30 {114}

30{ 114}

30 {114}

30 {114}

40.5 {153}

Number of condenser fans

1

2

2

2

2

2

4

Condenser fan power Hp {kW}

0.063 {0.047}

0.063 {0.047} 0.063 {0.047}

0.063 {0.047}

0.063 {0.047} 0.50 {0.047}

0.50 {0.047}

Condenser air flow ft

3

/min {l/min}

1050 {496}

1704 {804}

2420 {1142}

4237 {2000}

4237 {2000}

5300 {2501}

8400 {3964}

Dimensions inches {mm}

A - Height

**

45 {1143}

48 {1129}

48 {1129}

56 {1422}

56 {1422}

70 {1778}

76 {1930}

B - Depth

32 {812}

44 {1118}

44 {1118}

48 {1219}

48 {1219}

48 {1219}

48 {1219}

C - Width

29 {737}

29 {737}

29 {737}

34 {737}

34 {737}

34 {737}

40{1016}

Weight lb {kg}

Shipping weight

750 {340}

1000 {454}

1000 {454}

1200 {544}

1200 {544}

1400 {635}

1600 {726}

Installed weight

610 {277}

830 {376}

830 {376}

1030 {467}

1030 {467}

1230 {558}

1430 {649}

Utility Requirements

Water connections NPT (female) inches

1

1

1

1.5

1.5

1.5

1.5

Process water inches

1

1

1

1.5

1.5

1.5

1.5

Voltages running and full load amps

run

full

run

full

run

full

run

full

run

full

run

full

run

full

208V/3 phase/60hz

11.7

18.3

16.1

18.6

21.0

27.0

27.8

32.3

31.0 34.5

63.0

69.6

90.8

97.8

230V/3 phase/60hz

10.6

16.6

14.6

16.8

19.0

24.4

25.2

29.2

28.0 31.2

57.0

63.0

82.2

88.5

460V/3 phase/60hz

5.3

8.3

7.3

8.4

9.5

12.2

12.6

14.6

14.0 15.6

28.5

31.5

41.1

44.3

575V/3 phase/60hz

4.2

6.6

5.8

6.7

7.6

9.8

10.1

11.7

11.2 12.5

22.8

25.2

32.9

35.4

SPECIFICATION NOTES

* Based on 50° F (10° C) water temperature (100% water) leaving the chiller, standard pump selections, 95° F (35° C) ambient air conditions.

Consult factory for other conditions.

† Standard pump selection. Larger pumps available as options.
‡ Based on 50° F water temperature leaving the chiller 60° F (15° C) water temperature returning to the chiller.
§ Pressure at pump discharge.
** Control can be extended upward approximately 11 inches, which may or may not increase the overall height of the unit.

Specifications may change without notice. Check with a Conair representative for the most current information.

Flow Rate (gpm)

60 HZ PUMP PERFORMANCE CURVES

Pressure (psi)

Advertising
This manual is related to the following products:

MPW