Connecting process and water lines, Connecting the proces and water supply lines -4, Connecting the water supply -4 – Conair MPA User Manual

Page 20: Onnecting, Rocess and, Ater, Upply, Ines

Advertising
background image

The chiller process inlets and outlets must be connected to the
plumbing that will circulate the temperature-controlled water
or fluid through the process. Cooling water inlets and outlets
are connected to the cooling water supply.

Remove the shipping pipe plug

from the female

connections on the back of the chiller.

Install pipe to the rear of the chiller.

Use appropriately sized male NPT piping for the process
connections and the MPW condenser water connections.

Pipe and pipe threads must be clean and new. Clean
threads with solvent, removing all oil, grease and dirt.
Allow the threads to dry before proceeding.

Coat the pipe threads with thread sealant.

Follow the sealant manufacturer’s directions.

Connect the male pipe to the appropriate
female connection on the back of the unit

.

Connections are labeled on the chiller. Start by hand until
the threads engage, then use a pipe wrench to tighten the
connection only enough to prevent leaks.
Do not over-tighten!

C

ONNECTING

P

ROCESS AND

W

ATER

S

UPPLY

L

INES

microKool Portable Chillers

UGH004/0999

3-4

I

NSTALLATION

1

2

3

4

Tools for installation:

Pipe wrench large enough

for a 2-inch pipe

Premium quality Teflon

thread sealant

Process connections (NPT):

MPW-1.5 MPW-2 MPW-3 MPW-4 MPW-5 MPW-7.5 MPW-10

MPA-1.5

MPA-2

MPA-3

MPA-4

MPA-5

MPA-7.5

MPA-11

1 in.

1 in.

1 in.

1.5 in.

1.5 in.

1.5 in.

1.5 in.

Condenser water connections (NPT):

MPW-1.5 MPW-2 MPW-3 MPW-4 MPW-5 MPW-7.5 MPW-10

1 in.

1 in.

1 in.

1.5 in.

1.5 in.

1.5 in.

1.5 in.

NOTE: Make sure the
chiller tank is full of
process fluid before
you begin operating.
Use a glycol mixture if
operating temperatures
are below 45° F. See

F

REEZE

P

ROTECTION

R

EQUIREMENTS

.

Tank

fill port

Condenser

water in

From

Process

Condenser

water out

Condenser water
connections on
MPW models only

To

Process

Tank level

sight glass

Advertising
This manual is related to the following products:

MPW