Changing temperature units, Changing temperature units -9, Hanging – Conair MPA User Manual

Page 25: Emperature, Nits

Advertising
background image

UGH004/0999

microKool Portable Chillers

C

HANGING

T

EMPERATURE

U

NITS

The temperature units are factory-set as degrees Celsius or
degrees Fahrenheit, as specified when the unit was ordered.

When the chiller is on, the indicator lights to the right of the
Actual temperature display on the control panel will show
which temperature unit has been set.

To change this setting, move Dip Switch 1 on the control
circuit board.

Disconnect and lock out main power

to the

chiller.

Open the electrical enclosure.

Change Dip Switch 1 to:

OFF for °F

ON for °C

Close the electrical enclosure

and restore main

power to begin operating.

1

2

3

4

5

6

7

8

1

2

3

1

2

3

4

5

6

7

8

4

I

NSTALLATION

3-9

WARNING: Electric shock hazard

This equipment is powered by high voltage. Always
disconnect and lock out the main power source
before opening the unit or the electrical enclosure to
modify factory settings. Failure to disconnect and
lock out the main power source can result in severe
personal injury.