Calibrating temperature sensors, Calibrating temperature sensors -12, Calibrating temperature – Conair MPA User Manual

Page 54: Sensors -12, Alibrating, Emperature, Ensors

Advertising
background image

The microKool chillers use thermocouples to sense the tem-
perature in the return and supply process lines. These thermo-
couples should be calibrated annually, or when a new thermo-
couple is installed, to ensure correct operation.

The chiller’s Calibration Mode provides zero and span calibra-
tion of both the supply and return line thermocouples. You
access the Calibration Mode while in Test Mode.

Enable Test Mode.

See

P

ERFORMING

S

YSTEM

T

ESTS

.

Press any button to display the first test menu.

Select the Calibration Mode menu.

Press and hold the Setpoint key for 3 seconds to index
to each test menu until the controller indicates “SC.L” in
the Actual display.

Release the Setpoint key.

You are now in calibration mode. Each press and release
of this key will exit the current calibration and start the
next calibration. The table below lists the calibrations that
will be performed.

Using the thermocouple calibrator, apply the
appropriate temperature to the control input.

C

ALIBRATING

T

EMPERATURE

S

ENSORS

microKool Portable Chillers

UGH004/0999

5-12

M

AINTENANCE

Special Tools Needed:

thermocouple calibrator

1

2

3

4

5

SETPOINT

ACTUAL

CALIBRATION

DISPLAY

DISPLAY

Zero Calibrate Supply Sensor

32° F (0° C)

SC.L

Zero Calibrate Return Sensor

32° F (0° C)

rC.L

Span Calibrate Supply Sensor

510° F (266° C)

SC.H

Span Calibrate Return Sensor

510° F (266° C)

rC.H