Repair procedures, Checking / replacing fuses, Checking and replacing fuses -13 – Conair MPA User Manual

Page 69: Checking and replacing fuses .6-13, Hecking and, Eplacing, Uses, Fault and correct it. see, Heck, Ing and

Advertising
background image

UGH004/0999

microKool Portable Chillers

T

ROUBLESHOOTING

6-13

C

HECKING AND

R

EPLACING

F

USES

IMPORTANT:

Always

refer to the wiring dia-
grams that came with
your chiller to locate spe-
cific electrical compo-
nents. Illustrations in the
User Guide are intended
to be representative only.

This procedure covers the factory-installed fuses on the unit’s
motherboard. If you have installed an electrical disconnect or
emergency stop switch, additional fuses and/or breakers may
have been used elsewhere in the in the main power circuit.

To replace a blown fuse:

Disconnect and lockout the main power.

Open the electrical enclosure door.

Turn the screw

on the front panel counterclockwise to open.

Replace the fuse.

The fuses are located on the mother-

board and are labeled and identified on the orange shield.

Close the electrical enclosure and restart the unit.

If fuses continue to fail:

❒ Verify that the unit is receiving the correct voltage.

Check the voltage, phasing and amperage ratings on
the unit’s nameplate.

❒ Verify that the unit’s transformer is operating correctly.

Check for proper voltage (120V 10%) to the voltage
sensing device for the fuse location.

❒ Check all wiring referencing the fusing location for

loose connections, damage or improper grounding.
Verify that the correct device is being used for this fuse
location. See

D

ISABLING OR

E

NABLING

O

UTPUT

M

ONITORS

in the

M

AINTENANCE

section.

1

2

3

4

CONFIGURATION

DIP SWITCH

OFF

ON

4
3
2
1

4
3
2
1

UNLDR 1/ VENT 2 SOL +
UNLDR 1/ VENT 2 SOL

UNLDR 2/ COOL 1 SOL +
UNLDR 2/ COOL 1 SOL

F5

F4

F2

PUMP
PUMP

PUMP OL
PUMP OL

6
5
4
3
2
1

4
3
2
1

6
5
4
3
2
1

F3

4
3
2
1

F6

PMP AUX
PMP AUX

1FS/ PURGE/ COMP AUX

1FS/ COMP AUX

PUMPDOWN
PUMPDOWN

HEAT/COMP
HEAT/COMP

HTS/COMP OL
HTS/COMP OL

N
C

NC
NO

C

110V

ALARM

LLS/PURGE 3SOL
LLS/PURGE 3SOL +

PURGE 4SOL

PURGE 4 SOL +

3 PHASE INPUT

TCPL'S

SUP RET

A

C

IN 4

A

C

IN + 3

A

C

OUT 2

A

C

OUT + 1

F1

LLS/WPS

LLS/WPS

A

U

T

OST

AR

T

A

U

T

OST

AR

T

HPS/LPS

HPS/LPS

OPS

OPS

F

S

TAT

F

S

TAT

L1

L2

L3

6

5

4

3

2

1

4

3

2

1

Y

R

R

Y

1 2 3 4 5 6 7 8

1 2 3 4

(-2) CONTR

O

L

OPER PNL CABLE

+ 120 Ohm

+

TR

TR

GND

GND

+

TR

TR

120 Ohm

1

2

3

4

5

6

7

8

Fuse 1
Control
power

Fuse 5
Unloader valve 1

Fuse 4
Unloader valve 2

Fuse 2
Pump

Fuse 3
Compressor

Fuse 6
Level switch

WARNING:

Shock Hazard

Only qualified service
personnel familiar with
electrical testing and
industrial equipment
should examine and
correct problems that
require opening the
unit with power on to
diagnose the cause of
a problem.

Advertising
This manual is related to the following products:

MPW