The compressor may be located in the compressor electrical
enclosure or in the main chiller electrical enclosure, depend-
ing on the model of your chiller.

The compressor contactor should be replaced if:
● You have checked the amp draw on each of the three-phase

legs and discovered a voltage imbalance greater than 10%.

● You have checked the continuity and found that ohms at

the coil equal zero.

To replace the compressor contactor:

Disconnect and lockout the main power.

Open the electrical enclosure.

Turn the screw on

the front panel counterclockwise to open.

Disconnect the wires from the compressor con-
tactor contactor.

Label the wires to ensure you can

connect them correctly to the new contactor.

Remove and discard the old contactor.

Reverse this procedure to install the new con-
tactor.

Make sure the wires are connected correctly

.

microKool Portable Chillers

UGH004/0999

6-16

T

ROUBLESHOOTING

1

2

3

4

5

IMPORTANT:

Always

refer to the wiring dia-
grams that came with
your chiller to locate spe-
cific electrical compo-
nents. Illustrations in the
User Guide are intended
to be representative only.

WARNING:

Electrical Shock Hazard

Only qualified service personnel who have been

trained on electrical testing and the procedures for
avoiding the hazards should diagnose or correct prob-
lems that require opening the unit with power on.

R

EPLACING THE

C

OMPRESSOR

C

ONTACTOR