Replacing the freezestat, Replacing the freezestat -18, Failed see – Conair MPA User Manual

Page 74: Eplacing the, Reezestat

Advertising
background image

microKool Portable Chillers

UGH004/0999

6-18

T

ROUBLESHOOTING

The freezestat unit is a bulb and capillary thermostat. To
replace the unit:

Shut down the chiller and disconnect the
process fluid lines.

Disconnect and lockout the power supply.

Drain the tank
of all fluid

through

the drain valve in the
base of the tank.

Locate the
freezestat bulb.

The bulb sensor is
located on the
process piping just
after the evaporator.

Remove the insulation around the bulb.

Detach the bulb from the process line.

Open the chiller electrical enclosure and locate
the freezestat unit.

Disconnect freezestat unit wires from their ter-
minals.

Mark the wires so that you can easily reconnect

the new unit to the appropriate terminals..

Loosen the screws holding the freezestat unit to
the electrical panel.

Remove the entire freezestat unit.

Threat the bulb and capillary through the raceway.

Reverse the process to install the new unit.

Be

sure to insert the bulb sensor completely into the process
piping well and replace the insulation around the bulb.

R

EPLACING THE

F

REEZESTAT

1

2

3

4

5

WARNING:

Electrical shock hazard

Before attempting maintenance of any kind,
stop the unit and disconnect and lock out the
main power supply.

6
7

8

9

Drain valve

Evaporator

10

11

Advertising
This manual is related to the following products: