Appendix b, Spi command pairs, See the – Conair MPA User Manual

Page 77: Ppendix, For additional, Ommands, Upported by the, Onair micro, Spi c

Advertising
background image

UGH004/0999

C

HILLER

SPI C

OMMANDS

A

PPENDIX

B-1

The SPI commands supported by Conair microKool portable
chillers are listed in the following tables.

The standard required commands and three optional com-
mands are listed in the SPI Command Pairs table, along with
the Select and Poll command pairs in hexadecimal format.
Select commands set or change chiller functions. Poll com-
mands retrieve information from the chiller.

See the tables on the following pages for the SPI status words
and BIT positions for Process Status, Machine 1 Status and
Machine 2 status.

For more information on the SPI protocol, you can obtain the
SPI Communication Protocol Manual by contacting:

The Society of the Plastics Industry, Inc.
1801 K Street, NW, Suite 600K
Washington, D.C. 20006
(202) 974-5200

Fax: (202) 296-7005

www.plasticsindustry.org

SPI C

OMMANDS

S

UPPORTED BY

THE

C

ONAIR

MICRO

K

OOL

SPI Command Pairs

Portable chillers Device ID: hex 21

Commands

Select

Poll

Echo

0x21

0x21

- Select stores 4 bytes of information at the chiller; Poll retrieves it.

0x21

0x20

Setpoint Process Temperature

0x21

0x21

- Sets and retrieves the process temperature setpoint.

0x31

0x30

Alarm, High Temperature Deviation*

0x21

0x21

- Sets the alarm band temperature; retrieves setpoint + alarm band value.

0x33

0x32

Alarm, Low Temperature Deviation*

0x21

0x21

- Sets the alarm band temperature; retrieves setpoint + alarm band value.

0x35

0x34

Mode, Machine

0x21

0x21

- Start/stops the chiller; acknowledges alarms; retrieves run status

0x49

0x48

Version

0x21

- Retrieves 4 bytes of SPI version information.

0x22

Process Status

0x21

- Retrieves run status and alarm conditions.

0x40

Status, Machine 1

0x21

- Retrieves run status and alarm conditions.

0x42

Status, Machine 2

0x21

- Retrieves run status and alarm conditions.

0x44

Temperature, from Process

0x21

- Retrieves the actual temperature of fluid returning to the chiller.

0x72

* NOTE: Both High and Low Temperature Deviation commands set the
same variable. Use only one of these commands to avoid problems.