Spi status words, machine 2, Spi s, Tatus – Conair MPA User Manual

Page 80: Ords, Spi c, Ppendix, Status, machine 2

Advertising
background image

C

HILLER

SPI C

OMMANDS

UGH004/0999

A

PPENDIX

B-4

Status, Machine 2

Poll: 0x21 0x44

SPI STATUS WORD

Word BIT position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

EEprom error

SET SET

*

A/D converter error

SET SET

*

CJC Error

SET SET

*

RAM hardware

SET SET

*

ROM checksum

SET SET

*

Probe Failure

SET

SET SET

*

E/M Hi temp safety

*

Prog. Hi temp safety

*

Output monitor failure

SET

SET

*

Low water pressure

*

High deviation alarm

*

Low deviation alarm

*

Prog. Lo temp safety

*

Pump overload

SET

SET

*

Refrig. Pressure

SET

SET

*

Oil Safety

SET

SET

*

Compressor overload

SET

SET

*

Freeze Stat
Low water level

SET

SET

*

Test Mode

*

Phase error

*

NOTES:

*

The SPI I/O list defines the Processing bit as being cleared if the unit is not processing; otherwise it is SET.

Elsewhere on the chart:

If a bit is not shown to be SET, it is cleared.

The System Alarm bit is SET if an alarm is present. It is the logical OR of Process alarm and Machine alarm.

Processing, System Alarm, Process Alarm and Machine Alarm bits are repeated for Process Status, Machine 1

Status and Machine 2 Status.

SPI S

TATUS

W

ORDS

Open

Open

Reser

ved

Reser

ved

Reser

ved

Reser

ved

Reser

ved

Reser

ved

Reser

ved

Reser

ved

F

ault,

CAL

F

ault,

Sensor

Alarm,

Mac

hine

Alarm,

Pr

ocess

Alarm,

System

Pr

ocessing

Advertising
This manual is related to the following products:

MPW